Bryant DURAPAC PLUS SERIES 542J User Manual

Page 3

background image

3

Outlet grilles must not lie directly below unit discharge.

NOTE:

A 90-degree elbow must be provided in the ductwork

to comply with UL (Underwriters Laboratories) codes for use
with electric heat.

IV. STEP 4 — MAKE UNIT DUCT CONNECTIONS

Unit is shipped for thru-the-bottom duct connections. Duct-
work openings are shown in Fig. 6. Field-fabricated concen-
tric ductwork may be connected as shown in Fig. 7 and 8.

Attach all ductwork to roof curb and roof curb basepans.
Refer to installation instructions shipped with accessory roof
curb for more information.

V. STEP 5 — TRAP CONDENSATE DRAIN

See Fig. 4 or 5 and 9 for drain location. Plug is provided in
drain hole and must be removed when unit is operating. One

3

/

4

-in. half coupling is provided inside unit indoor air section

for condensate drain connection. An 8

1

/

2

in. x

3

/

4

-in. diameter

nipple and a 2-in. x

3

/

4

-in. diameter pipe nipple are coupled

to standard

3

/

4

-in. diameter elbows to provide a straight path

down through holes in unit base rails (see Fig. 10). A trap at
least 4-in. deep must be used.

WARNING:

For vertical supply and return units,

tools or parts could drop into ductwork and cause an
injury. Install a 90-degree turn in the return ductwork
between the unit and the conditioned space. If a
90-degree elbow cannot be installed, then a grille of
sufficient strength and density should be installed to
prevent objects from falling into the conditioned space.
Due to electric heater, supply duct will require
90-degree elbow.

23"

14 3/4"

6"

3 1/2"

FULLY INSULATED
SUPPLY PLENUM
1" INSULATION
1 1/2 # DENSITY,
STICK PINNED & GLUED

2" X 1/4
SUPPORT TYP.
STITCH WELDED

12" WIDE STANDING
SEAM PANELS

NOTE: CRRFCURB013A00 is a fully factory preassembled horizontal
adapter and includes an insulated transition duct. The pressure drop
through the adapter curb is negligible.

For horizontal return applications: The power exhaust and barometric

relief dampers must be installed in the return air duct.

Fig. 2 — Horizontal Supply/Return Adapter Installation

ACCESSORY

PACKAGE NO.

CURB

HEIGHT

DESCRIPTION

CRRFCURB013A00

1

-11

(584)

Pre-Assembled, Horizontal

Adapter Roof Curb

NOTES:

1. Dimensions in ( ) are in millimeters.
2. Refer to Table 1 for unit operating weights.
3. Remove boards at ends of unit and runners prior to rigging.
4. Rig by inserting hooks into unit base rails as shown. Use corner

post from packaging to protect coil from damage. Use bumper
boards for spreader bars.

5. Weights do not include optional EconoMi$erIV. See Table 1 for

EconoMi$erIV weight.

6. Weights given are for aluminum indoor coil plate fins and copper

outdoor coil plate fins. Weights of other metal combinations are
listed in Table 1.

Fig. 3 — Rigging Details

UNIT 542J

MAXIMUM

SHIPPING WEIGHT

DIMENSION A

lb

kg

ft-in.

mm

150

1895

860

3-1

948

180

2205

1000

3-6

1059

CAUTION:

All panels must be in place when rigging.