B. EconoMi$erIV Standard Sensors

Outdoor Air Temperature (OAT) Sensor

The outdoor air temperature sensor (HH57AC074) is a 10 to
20 mA device used to measure the outdoor-air temperature.
The outdoor-air temperature is used to determine when the
EconoMi$erIV can be used for free cooling. The sensor must
be field-relocated. See Fig. 20. The operating range of tem-
perature measurement is 40 to 100 F.

Supply Air Temperature (SAT) Sensor

The supply air temperature sensor is a 3 K thermistor
located at the inlet of the indoor fan. See Fig. 21. This sensor
is factory installed. The operating range of temperature
measurement is 0° to 158 F. See Table 6 for sensor tempera-
ture/resistance values.

The temperature sensor looks like an eyelet terminal with
wires running to it. The sensor is located in the “crimp end”
and is sealed from moisture.

Low Temperature Compressor Lockout Switch

The EconoMi$erIV is equipped with an ambient tempera-
ture lockout switch located in the outdoor air stream which
is used to lockout the compressors below a 42 F ambient tem-
perature. See Fig. 20.

Table 6 — Supply Air Sensor Temperature/

Resistance Values

C. EconoMi$erIV Control Modes

Determine the EconoMi$erIV control mode before set up of the
control. Some modes of operation may require different sensors.
Refer to Table 7. The EconoMi$erIV is supplied from the factory
with a supply air temperature sensor, a low temperature com-
pressor lockout switch, and an outdoor air temperature sensor.
This allows for operation of the EconoMi$erIV with outdoor air
dry bulb changeover control. Additional accessories can be
added to allow for different types of changeover control and
operation of the EconoMi$erIV and unit.

Outdoor Dry Bulb Changeover

The standard controller is shipped from the factory config-
ured for outdoor dry bulb changeover control. The outdoor
air and supply air temperature sensors are included as stan-
dard. For this control mode, the outdoor temperature is com-
pared to an adjustable set point selected on the control. If the
outdoor-air temperature is above the set point, the
EconoMi$erIV will adjust the outdoor-air dampers to mini-
mum position. If the outdoor-air temperature is below the set
point, the position of the outdoor-air dampers will be con-
trolled to provide free cooling using outdoor air. When in this
mode, the LED next to the free cooling set point potentiome-
ter will be on. The changeover temperature set point is con-
trolled by the free cooling set point potentiometer located on
the control. See Fig. 23. The scale on the potentiometer is A,
B, C, and D. See Fig. 24 for the corresponding temperature
changeover values.

Differential Dry Bulb Control

For differential dry bulb control the standard outdoor dry
bulb sensor is used in conjunction with an additional acces-
sory return air sensor (part number CRTEMPSN002A00).
The accessory sensor must be mounted in the return
airstream. See Fig. 25.

In this mode of operation, the outdoor-air temperature is
compared to the return-air temperature and the lower tem-
perature airstream is used for cooling. When using this mode
of changeover control, turn the free cooling/enthalpy set point
potentiometer fully clockwise to the D setting. See Fig. 23.

Table 7 — EconoMi$erIV Sensor Usage

*CRENTDIF004A00 and CRTEMPSN002A00 accessories are used on many different base units. As such, these kits may contain parts that will not be needed for

installation.

†CGCDXSEN004A00 is an accessory CO

2

sensor.

**CGCDXASP001A00 is an accessory aspirator box required for duct-mounted applications.

TEMPERATURE (F)

RESISTANCE (ohms)

–58

200,250

–40

100,680

–22

53,010

–4

29,091

14

16,590

32

9,795

50

5,970

68

3,747

77

3,000

86

2,416

104

1,597

122

1,080

140

746

158

525

176

376

185

321

194

274

212

203

230

153

248

116

257

102

266

89

284

70

302

55

APPLICATION

ECONOMI$ERIV WITH OUTDOOR AIR

DRY BULB SENSOR

ECONOMI$ERIV WITH SINGLE

ENTHALPY SENSOR

Accessories Required

Accessories Required

Outdoor Air Dry Bulb

None. The outdoor air dry bulb sensor is factory installed.

CRTEMPSN002A00*

Differential Dry Bulb

CRTEMPSN002A00*

(2) CRTEMPSN002A00*

Single Enthalpy

HH57AC078

None. The single enthalpy sensor is factory installed.

Differential Enthalpy

HH57AC078

and

CRENTDIF004A00*

CRENTDIF004A00*

CO

2

for DCV Control using a

Wall-Mounted CO

2

Sensor

CGCDXSEN004A00

CO

2

for DCV Control using a

Duct-Mounted CO

2

Sensor

CGCDXSEN004A00†

and

CGCDXASP001A00**