Power Exhaust (output):

Connect the accessory Power

Exhaust contactor coil(s) per Fig. 46.

Power Exhaust

J11-3

C

TAN

PEC

CTB

THERMOSTAT

GRA

C10362

Fig. 46 -- RTU--MP Power Exhaust Connections

Space Relative Humidity Sensor -- The RH sensor is not

used with 548J*14D models at this time.

Communication Wiring -- Protocols

General —
Protocols are the communication languages spoken by

control devices. The main purpose of a protocol is to

communicate information in the most efficient method

possible. Different protocols exist to provide different

kinds of information for different applications. In the BAS

application, many different protocols are used, depending

on manufacturer. Protocols do not change the function of

a controller; just make the front end user different.
The RTU--MP can be set to communicate on four different

protocols: BACnet, Modbus, N2, and LonWorks. Switch 3

(SW3) on the board is used to set protocol and baud rate.

Switches 1 and 2 (SW1 and SW2) are used to set the

board’s network address. See Fig. 47 for the switch setting

per protocol. The 3rd party connection to the RTU--MP is

through plug J19.
NOTE: Power must be cycled after changing the SW1--3
switch settings.
Refer to the RTU--MP 3rd Party Integration Guide for

more detailed information on protocols, 3rd party wiring,

and networking.
Local Access —

BACview

6

Handheld:

The BACview

6

is a keypad/display

interface used to connect to the RTU--MP to access the

control information, read sensor values, and test the RTU,

see Fig. 48. This is an accessory interface that does not

come with the MP controller and can only be used at the

unit. Connect the BACview

6

to the RTU--MP’s J12 local

access port. There are 2 password protected levels in the

display (User and Admin). The user password is defaulted

to 0000 but can be changed. The Admin password is 1111

and cannot be changed. There is a 10 minute auto logout

if a screen is idle. Contact your Bryant applications

engineer for details on navigation and screen content.

Virtual BACview:

Virtual BACview is a freeware computer

program that functions as the BACview

6

Handheld. The

USB Link interface (USB--L) is required to connect a

computer to the RTU--MP board. The link cable connects

a USB port to the J12 local access port. This program

functions and operates identical to the handheld.
RTU--MP Troubleshooting —

Communication LEDs

The LEDs indicate if the

controller is speaking to the devices on the network. The

LEDs should reflect communication traffic based on the

baud rate set. The higher the baud rate the more solid the

LEDs will appear.

SW3 Protocol Selection

PROTOCOL

DS8

DS7

DS6

DS5

DS4

DS3

DS2

DS1

BACnet MS/TP

(Master)

Unused

OFF

OFF

OFF

ON

OFF

Select Baud Select Baud

Modbus

(Slave)

Unused

OFF

OFF

ON

ON

OFF

Select Baud Select Baud

N2

(Slave)

Unused

OFF

OFF

OFF

ON

ON

OFF

OFF

LonWorks

Unused

ON

ON

OFF

ON

OFF

OFF

OFF

NOTE:

DS = Dip Switch
BACnet MS/TP SW3 example shown

Baud Rate Selections

BAUD RATE

DS2

DS1

9600

OFF

OFF

19,200

ON

OFF

38,400

OFF

ON

76,800

ON

ON

C07166

Fig. 47 -- RTU--MP SW3 Dip Switch Settings

548J

*14D