17

HEATER
MOUNTING
BRACKET

HEATER
MODULE
(LOCATION 2)

HEATER
MODULE
(LOCATION 1)

SINGLE POINT
BOX
MOUNTING
SCREW

SINGLE
POINT BOX

HEATER
COVERS

MANUAL RESET
LIMIT SWITCH

DISCONNECT
MOUNTING
LOCATION

C10029

Fig. 29 -- Typical Component Location

Single Point Boxes

When heaters are installed, power wiring to both heaters

and the rest of the unit is connected via the single point

box accessory, which will be installed directly under the

unit control box, just to the left of the partition separating

the indoor section (with electric heaters) from the outdoor

section. The single point box has a hinged access cover.

See Fig. 29. The single point box also includes pigtails to

complete the wiring between the single point box and the

unit’s main control box terminals. Refer to the accessory

heater and Single Point Box installation instructions for

details on tap connections.

ALLIED PA

MODEL NO.

ERIAL NO.

CORP.

11

13

21

23

OD

22.2

3

1

23

ISTED AIR

NDITIONING

UIP ACCESS
346N.

P / N

2-

5610-4

REV

1

1

13

2

1

2

3

CONTROL
BOX

BUSHING

SINGLE
POINT BOX
MOUNTING
SCREWS

FOAM
BUSHING

DRIP BOOT
BRACKET
MOUNTING
SCREWS

HEATER
RELAYS

POWER
WIRES

HEATER
MOUNTING
SCREWS

C08136

Fig. 30 -- Typical Single Point Installation

Heater and Supplementary Fuses —
When the unit MOCP device value exceeds 60--A,

unit--mounted supplementary fuses are required for each

heater circuit. These fuses are included in accessory

Single Point Boxes, with power distribution and fuse

blocks.
All fuses on 548J units are 60--A. (Note that all heaters are

qualified for use with a 60--A fuse, regardless of actual

heater ampacity, so only 60--A fuses are necessary.)

Heater Low--Voltage Control Connections —
One or two heaters can be installed in the unit. Use the

wiring procedure listed below for each heater as

determined by the number of stages in the heater.
Single Stage Heaters: Single--stage heaters will have an

orange and a brown control wire. Connect these to the

orange and brown wires located on TB4.
Two Stage Heaters: Two--stage heaters will have orange,

purple, red and brown wires. The orange and the purple

are the control wires and the red and brown wires feed the

safety circuit. Connect both the orange and the purple

wires to the orange wire locations of TB4. Connect the

red and brown wires to red and brown wires on TB4. If

more than one heater is installed, repeat the wiring

procedure for the second heater. The 3 locations across

the top of TB4 do allow a switch to be installed in series

with some of the heaters in order to add additional heater

control.

548J

*14D