Economizer Hood and Two--Position Hood —
NOTE
: If the power exhaust accessory is to be installed
on the unit, the hood shipped with the unit will not be
used and must be discarded. Save the aluminum filter for

use in the power exhaust hood assembly.

1. The indoor coil access panel will be used as the top of

the hood. If the panel is still attached to the unit, re-

move the screws along the sides and bottom of the

panel. See Fig. 11.

SIDE
PANEL

INDOOR
COIL
ACCESS
PANEL

INDOOR
COIL
ACCESS
PANEL

CAULK
HERE

TOP
PANEL

RAIN DEFLECTORS

C10007

Fig. 11 -- Indoor Coil Access Panel Relocation

2. Swing out indoor coil access panel and insert the

hood sides under the panel (hood top). Be careful not

to lift the panel too far as it might fall out. Use the

screws provided to attach the hood sides to the hood

top. Use screws provided to attach the hood sides to

the unit. See Fig. 12.

TOP
PANEL

INDOOR COIL
ACCESS PANEL

SCREW

HOOD DIVIDER

LEFT
HOOD
SIDE

C10008

Fig. 12 -- Economizer Hood Construction

3. Remove the shipping tape holding the economizer

barometric relief damper in place.

4. Insert the hood divider between the hood sides. See

Fig. 12 and 13. Secure hood divider with 3 screws on

each hood side. The hood divider is also used as the

bottom filter rack for the aluminum filter.

5. Attach the post that separates the filters with the

screws provided.

6. Open the filter clips which are located underneath the

hood top. Insert the aluminum filters into the bottom

filter rack (hood divider). Push the filter into position

past the open filter clips. Close the filter clips to lock

the filters into place. See Fig. 13.

7. Install the two rain deflectors on the edge of the hood

top as shown in Fig. 11.

DIVIDER

BAROMETRIC
RELIEF

CLEANABLE
ALUMINUM
FILTER

FILTER

HOOD

FILTER
CLIP

OUTSIDE
AIR

C10009

Fig. 13 -- Economizer Filter Installation

8. Caulk the ends of the joint between the unit top panel

and the hood top as shown in Fig. 11.

9. Replace the filter access panel.

Step 9 — Install External Condensate Trap and

Line

The unit has one

3

/

4

-in. condensate drain connection on

the end of the condensate pan and an alternate connection

on the bottom. See Fig. 14. Unit airflow configuration

does not determine which drain connection to use. Either

drain connection can be used with vertical or horizontal

applications.

When using the standard side drain connection, ensure the

red plug in the alternate bottom connection is tight. Do

this before setting the unit in place. The red drain pan can

be tightened with a

1

/

2

--in. square socket drive extension.

To use the alternate bottom drain connection, remove the

red drain plug from the bottom connection (use a

1

/

2

--in.

square socket drive extension) and install it in the side

drain connection.

DRAIN

(FACTORY-INSTALLED)

PLUG

CONDENSATE PAN (SIDE VIEW)

STANDARD

SIDE DRAIN

ALTERNATE

BOTTOM DRAIN

C08021

Fig. 14 -- Condensate Drain Pan (Side View)

548J

*14D