RTU--MP Control System

The RTU--MP controller, see Fig. 33, provides expanded

stand--alone operation of the HVAC system plus

connection and control through communication with

several Building Automation Systems (BAS) through

popular third--party network systems. The available

network systems are BACnet MP/TP, Modbus and

Johnson J2. Communication with LonWorks is also

possible by adding an accessory interface card to the

RTU--MP. Selection of the communication protocol and

baud rate are made at on--board DIP switches.

The RTU--MP control is factory--mounted in the

548J*14D unit’s main control box, to the left of the CTB.

See Fig. 34. Factory wiring is completed through

harnesses connected to the CTB. Field connections for

RTU--MP sensors will be made at the Phoenix connectors

on the RTU--MP board. The factory--installed RTU--MP

control includes the supply--air temperature (SAT) sensor.

The outdoor air temperature (OAT) sensor is included in

the FIOP/accessory EconoMi$ert2 package.

Refer to Table 2, RTU--MP Controller Inputs and Outputs

for locations of all connections to the RTU--MP board.