beautypg.com

Bryant 373LAV User Manual

Page 6

background image

IV.

RETURN AIR CONNECTIONS

The return-air duct must be connected to return-air opening (inlet)
provided as shown in Fig. 1. DO NOT cut into casing sides or back
to attach any portion of return-air duct. Bypass humidifier connec-
tions should be made at ductwork or coil casing sides exterior to
furnace.

V.

DOWNFLOW INSTALLATION

NOTE:

This furnace is approved for use on combustible materials

or wood flooring. A factory accessory floor base, as listed on the
furnace rating plate, MUST be used. A factory accessory floor
base is not required when this furnace is installed on manufactur-
er’s Coil Assembly Part No. CD5 or CK5, or Coil Box Part No.
KCAKC is used.

1. Determine application being installed from Table 3.

2. Construct hole in floor per dimensions specified in Table 3

and Fig. 5.

3. Construct plenum to dimensions specified in Table 3.

4. If downflow subbase (KGASB) is used, install as shown in

Fig. 6.

If coil assembly CD5, CK5, or Coil Box KCAKC is used,
install as shown in Fig. 7.

VI.

HORIZONTAL ATTIC INSTALLATION

WARNING:

DO NOT install the furnace on its back;

safety control operation will be adversely affected. Never
connect return-air ducts to the sides or back of the
furnace. Failure to follow this warning could result in fire,
personal injury, or death.

The furnace can be installed horizontally on either the left-hand
(LH) or right-hand (RH) side. A typical attic installation is shown
in Fig. 8.

Fig. 3—Confined Space: Air for Combustion and Ventilation

from an Unconfined Indoor Space

A93387

RETURN

AIR

6

MIN

(FRONT)

SUPPLY AIR

VENT THROUGH ROOF
(CATEGORY I)

1 SQ IN.
PER 1000
BTUH* IN DOOR

OR WALL

12

MAX

1 SQ IN.
PER 1000
BTUH* IN DOOR

OR WALL

12

MAX

INTERIOR

HEATED

SPACE

* Minimum opening size is 100 sq in. with
minimum dimensions of 3 in.

Minimum of 3 in. when type B-1 vent is used.

UNCONFINED
SPACE

Fig. 4—Confined Space: Air for Combustion and Ventilation

from Outdoors

A93388

DUCTS TO

OUTDOORS

1 SQ IN.
PER 4000
BTUH

*

RETURN

AIR

VENT
THROUGH
ROOF
(CATEGORY I)

D

B

A

C

E

1 SQ IN.
PER 4000
BTUH

DUCT

TO

OUTDOORS

SUPPLY AIR

1 SQ IN.
PER 2000
BTUH*

DUCTS

TO

OUTSIDE

12

MAX

12

MAX

CONFINED

SPACE

12

MAX

12

MAX

1 SQ IN.
PER 4000
BTUH

*

OUTDOORS

1 SQ IN.
PER 4000
BTUH

*

1 SQ IN.
PER 2000
BTUH*

12

MAX

Use any of the following
combinations of openings:
A & B C & D D & E F & G

NOTE:

*Minimum dimensions of 3 in.

F

G

TABLE 2—MINIMUM FREE AREA OF COMBUSTION AIR OPENING*

373LAV

FURNACE

INPUT

(BTUH)

AIR FROM INDOOR

UNCONFINED SPACE

OUTDOOR AIR THROUGH

VERTICAL DUCTS

OUTDOOR AIR THROUGH

HORIZONTAL DUCTS

OUTDOOR AIR THROUGH

SINGLE DUCT

Free Area

of Opening

(Sq In.)

Free Area of

Opening and Duct

(Sq In.)

Round

Pipe

(In. Dia)

Free Area of

Opening and Duct

(Sq In.)

Round

Pipe

(In. Dia)

Free Area of

Opening and Duct

(Sq In.)

Round

Pipe

(In. Dia)

46,000

100

11.50

4

23.0

6

15.33

5

69,000

100

17.25

5

34.5

7

23.00

6

92,000

100

23.00

6

46.0

8

30.67

7

115,000

115

28.75

7

57.5

9

38.33

7

135,000

135

33.75

7

67.5

10

45.00

8

* Free area shall be equal to or greater than the sum of the areas of all vent connections in the confined space. Opening area must be increased, if other gas appliances
in the space require combustion air.

—6—