commercially available mild detergent. It is possible to remove any
dry dirt by knocking the mat slightly, vacuum cleaning it or blowing
it out.

CAUTION

Damage to the filter mat.

Do not wring the filter mat. Avoid too solid a water jet.

. If the filter mat is oily or greasy, replace.

11.2 Maintenance

The components around the external air circuit require
maintenance and cleaning depending upon the ambient
conditions (see Section 11.1).
After each service, normal running of fans should be checked.

12 Stopping

If the air/air heat exchanger is not in use for a longer period,
disconnect it. Ensure that unauthorised persons cannot start the
air/air heat exchanger. When the air/air heat exchanger is no
longer needed, it must be disposed of by authorized specialist
personnel in accordance with all applicable environmental
protection regulations. (see also Section 4, General Information).

13 What to do if ...

... in spite of your care and attention a fault occurs?

Check the following points first. If the fault is not then cleared,

call an authorized specialist.

13.1 General errors

- No message via the service indicator

Fault

Possible cause(s)

Remedy

Internal fan is not running

Internal fan faulty

Call authorized specialist, replace internal fan

Power abnormal

Check the power

High temperature alarm, external fan
is running

Threshold values for usage exceeded

Check ambient temperature and internal heat load

Incorrect temperature setting

Increase alarm set point or decrease control set
point

Heat exchanger contaminated

Clean heat exchanger

Filter screen contaminated

Clean filter screen

Internal fan faulty

Call authorized specialist, replace fan

High temperature alarm, external fan
is not running

External fan faulty

Call authorized specialist, replace fan

Power faulty

Check power

Incorrect temperature setting

Increase alarm set point or decrease control set
point

Control temperature thermostat faulty

Call authorized specialist, replace thermostat

14 Warranty Condition

Warranty becomes null and void:

— In case of improper usage of the unit, noncompliance with operating conditions or non observance of instructions;
— If operated in rooms in which corrosives or acids are present in the atmosphere;
— In case of damage caused by contaminated or jammed air filters;
—— If a non-authorised person interrupts the temperature control circulation, modifies the unit or changes the serial number;
— In case of damage caused by transport or by accidents;
— For the exchange of parts by non-authorized personnel.

In order to maintain your warranty rights please observe the following when returning the unit:
— Include a detailed description of the defect and the DRU(RMA) number issued by Pfannenberg with the cooling unit.
— Enclose proof of delivery (delivery note or copy of invoice).
— Return the unit together with all accessories; use the original packaging or packaging of equivalent quality, send the unit freight prepaid
and covered by adequate transport insurance. Observe the hints on transport mentioned in section 2.