beautypg.com

Pfannenberg PAI User Manual

Page 12

background image

12 / 46

685 408 005

nominal values indicated on the ID plate of the air/air heat
exchanger.
— The installation of the power cable is not subject to any special
requirements

Attention!

The air/air heat exchanger may be damaged if the voltage is too
high
Refers to air/air heat exchanger for nominal voltage 115V or
230V.

9 Operating Conditions

— Voltage must be within ± 10 % of the value indicated.
— Frequency must be within ± 3 Hz of the value indicated.

Ambient temperature must be below 55 °C (for options see
supplement).

— Use the unit such that the cooling capacity suits the actual

demand.

— Use genuine spare parts only.

10 Putting into operation and function

10.1 General remarks

The air/air heat exchanger is provided with a temperature control
system. The switch cabinet internal air temperature is measured
by thermostats. Different switch cabinet temperatures as well as
upper limit temperatures can be set (see accompanying
sheet also).Exceeding the limit temperature generates an alarm.

Warning: Ambient conditions and temperature in the
switch cabinet must be in accordance with the values
indicated in the supplement.

10.2 Centralised fault indication

The signaling of a fault in the air/air heat exchanger is effected
by the closing of a potential-free contact (see Sections 13).

10.3 Setting possibilities

By means of the thermostats, various switch cabinet temperatures

as well as alarm temperatures can be set. (see accompanying

supplement sheet also)

— The air to air heat exchanger control system includes a

mechanical thermostat that sets the target control

temperature inside the switch cabinet.

— The air to air heat exchanger control system also includes a

second mechanical thermostat that is used as high

temperature alarm device. This device generates alarm by

closing potential –free contact.

Thermostat Setting

1) Cabinet control temperature

















With the help of a screw driver, rotate the “stem” to the intended
target setting point. The setting point of this control temperature
may only be 5℃ lower than the alarm temperature. 10℃ is
suggested.

2) Alarm temperature
Using a screw driver, rotate the stem of the alarm mechanical
thermostat to the intended alarm setting point. The setting point on
the alarm thermostat may not be less than 5℃ higher than the
control setting point. 10℃ is suggested.

CAUTION: Changes to the thermostat set of the air/air
heat exchanger in the works may be made only by
authorised persons!

CAUTION: Control temperature may not be less than
maximum ambient temperature surrounding the switch
cabinet.

11 Cleaning and Maintenance

Hazard

Isolate the air/air heat exchanger from the mains before carrying
out any cleaning or maintenance operations.

11.1 Cleaning

The cleaning intervals depend upon the relevant operating
conditions. In particular observe the following instructions.
— Clean the heat exchanger regularly.
— Clean filter screen (If there is)
— Clean the heat exchanger using a soft brush or pressurized air.

Proceed as follows:

1) Disconnect the air/air heat exchanger from the power supply.
2) Remove external cover.
3) Clean filter screen.
4) Clean heat exchangers.

CAUTION

Protect the electric components against leakage.

CAUTION

Damage to heat exchanger

Do not use any pointed or sharp-edged
objects.

CAUTION

Damage to electric connections on the

covering hood
If the covering hood is removed, the electric plug-in
connections on the inside must be removed by hand.
During fitting do not forget to plug-in!

. If the units are provided with a front filter clean the filter mat
regularly. The cleaning intervals or the intervals for replacement of
the filter mat mainly depend upon ambient conditions (air
pollution).
. You can rinse the filter mat using water heated to 40 °C and

This manual is related to the following products: