WIKA operating instructions temperature switch model TSD-30

GB

11613025.02 12/2011 GB/D/F/E

6.4 Switching functions

Hysteresis function

If the temperature fluctuates around the set point, the hysteresis keeps

the switching status of the outputs stable. With increasing temperature,

the output switches when reaching the switch point (SP).

Contact normally open (HNO): active

Contact normally closed (HNC): inactive

With temperature falling again, the output will not switch back before

the reset point (RP) is reached.

Contact normally open (HNO): inactive

Contact normally closed (HNC): active

Window function

The window function allows for the control of a defined range.

When the temperature is between window High (FH) and window Low

(FL), the output switches on.

Contact normally open (FNO): active

Contact normally closed (FNC): inactive

When the temperature is outside window High (FH) and window Low

(FL), the output does not switch on.

Contact normally open (FNO): inactive

Contact normally closed (FNC): active

6. Commissioning, operation

Fig.: Hysteresis function

Fig.: Window function