WIKA operating instructions temperature switch model TSD-30
GB
11613025.02 12/2011 GB/D/F/E
6. Commissioning, operation
6.4 Parameters
Parameter Description
SP1/SP2
Hysteresis function: Switch point switching output (1 or 2)
FH1/FH2
Window function: Window high switching output (1 or 2)
RP1/RP2
Hysteresis function: Reset point switching output (1 or 2)
FL1/FL2
Window function: Window low switch output (1 or 2)
EF
Extended programming functions
RES
Return the set parameter to the factory settings
DS1/DS2
Switch delay time, which must occur without interruption before any electrical signal change occurs
(SP1 or SP2)
DR1/DR2
Switch delay time, which must occur without interruption before any electrical signal change occurs
(RP1 or RP2)
OU1
Switching function switching output (1 or 2)
OU2
HNO = hysteresis function, normally open
HNC = hysteresis function, normally closed
FNO = window function, normally open
FNC = window function, normally closed
UNIT
Changing units
(If the measuring range is outside the indication range, a unit switching is not possible and the UNIT
parameter is not indicated)
SETR
Measuring range scaling (analogue output)
“4 mA” or “0 V” determines at which temperature the output signal is to be 4 mA or 0 V.
“20 mA” or “10 V” determines at which temperature the output signal is to be 20 mA or 10 V.
OFS
Offset adjustment (3 % of span)
DISM
Display value in display mode
ACT = Actual temperature value; LOW, HIGH = Minimum, Maximum temperature value
OFF = display off;
SP1/FH1 = function switch point 1, RP1/FL1 = function reset point 1,
SP2/FH2 = function switch point 2, RP2/FL2 = function reset point 2
DISR
Rotate display indicator by 180°
RHL
Clear the Min- and Max-value memories
PAS
Password input, 0000 = no password; Password input digit by digit
TAG
Input of a 16-figure alphanumeric measuring point number