Transmitter for level measurement – WIKA 732.15.160 User Manual

Page 11

background image

Specifications

Models 891.44 and 892.44 (Ex Version)

Power supply U

B

for Non-Ex version

DC

12 V < U

B

≤ 30 V

for Ex version

see the section ‚Ex protection‘!

Permissible residual ripple

% of span/10 V

0.1

Supply voltage effect

% ss

10

Output signal

4 … 20 mA, 2-wire system

Permissible max. load R

A

for Non-Ex versions, Model 891.44:

R

A

≤ (U

B

- 12 V) / 0.02 A with R

A

in Ω and U

B

in Volt

for Ex versions, Model 892.44:

R

A

≤ (U

B

- 14 V) / 0.02 A with R

A

in Ω and U

B

in Volt

Effect of load

% of span

0.1

Output signal adjustment

Zero point, electrical

A

djustment of zero point through brief bridging of terminals 5 and 6,

or using the „scale selection switch“ option, selectable via button

1)

Scale selection

4 scales selectable via BCD switch

Linearity

% of span

1.0 (limit point calibration)

Permissible

ambient temperatures

°C

-40 … +80, -40 … +60 with oxygen

Compensated temp. range

°C

-40 … +80

Temperature coefficients in

compensated temp. range

Mean TK of zero

% of span/10 K

0.3

Mean TK of span

% of span/10 K

0.3

Ex protection

according to EC-Type Examination Certificate

BSV 08 ATEX E 018 X for Model 892.44

Ex certification

EEx II 2G EEx ia IIC T6

Conformity specifications

Power supply U

i

DC

14 … 30 V

Short circuit rating I

i

mA

max. 100

Rating P

i

W

max. 1

Internal capacitance C

i

nF

12

Internal inductance L

i

mH

negligible

Medium temperature

°C

-40 … +80, -40 … +60 with oxygen

Ambient temperature

°C

-40 … +60 (T6)

CE-Conformity

interference emission and immunity per EN 61326

Wiring

L-connector (screw terminals up to 2.5 mm²)

Wiring protection

protected against reverse polarity and overvoltage

Ingress protection

IP 65 per EN 60529 / IEC 529

Wiring details,

2-wire

11265191.07 12/2012 GB/D/F/I

Earth, connected

to case 2)

U

B

+/Sig+

Terminals 3, 4, 5 and 6: only for internal

application

0V/Sig-

WIKA operating instructions differential pressure gauge models 712.15.160, 732.15.160

11

GB

8. Transmitter for level measurement

1) Only possible within 30 seconds of connecting the supply voltage

2) This connection must not be used

for equipotential bonding. The

instrument must be incorporated in

the equipotential bonding via the

process connection.