WIKA Operating instructions DELTA-plus, DELTA-comb and DELTA-switch per ATEX

11242370 06/2007 GB/D/F

GB

3. Technical data and intended use / 4. Requirements for use ...

3. Technical data and intended use

Static pressure: 25 bar

Overpressure safety (either side): up to 25 bar max.

Operating temperature

Ambient

-10 … +70 °C

Medium

+90 °C maximum

Observe restrictions for use in potentially explosive atmospheres

(see section 4)

Pressure connection: 2 × G ¼ female

IP Ingress protection: IP 54 (EN 60 529 / IEC 529)

Permissible vibration levels at the mounting point

T

As a matter of principle the instruments should only be mounted in locations

without a vibration load.

T

Isolation from a mounting point exposed to vibration can be achieved, for

example, by mounting the pressure gauge to a solid wall and a flexible

capillary connecting the measuring point to the pressure gauge (see

section 5).

T

The following limits must not be exceeded:

Frequency range < 150 Hz

Acceleration

< 0.7 g (7 m/s

2

)

Electrical contact

(applies to Model 702.02/03.100 and 851.02.100)

Adjustable range: from 10 % to 100 % of span

Switching point adjustment: from the outside by means of setpoint screw(s)

Contact hysterisis: max. 5 % of full-scale value

!

Note

4. Requirements for use in potentially explosive

atmospheres

The built-in Reed contacts (applies to Model 702.02/03.100 and

851.02.100) do

not possess their own ignition source. For the

purposes of intrinsic safety they are 'simple apparatus' as defined

in EN 50 020.
When supplied from a tested and certified intrinsically safe circuit

(associated apparatus), these switches may be used in potentially

explosive atmospheres up to category 2 without having to take any

further measures.