6

.4 Parameter description

DPT

10 has general adjustment parameters which are also used for

other measuring principles as well as instrument-specific adjustment
parameters. The general adjustment parameters are described in the
operating instructions manual "Indicating and adjustment module".

The instrument-specific adjustment parameters are described in this
chapter.

Information:
If the adjustment limits of the adjustment parameters are exceeded,
the message "Outside parameter limits" appears. The editing
procedure can be aborted with [ESC] or the displayed limit value can
be accepted with [OK].

DPT

10 can be used for differential pressure, level as well as flow

measurement. The delivery status is level measurement. The selection
is made in the menu item "Application". Depending on the selected
application, the adjustment is carried out as zero/span or min./max.
adjustment.

Proceed as follows to switch over to the application differential
pressure or flow measurement:

1

Push the [OK] button in the measured value display, the menu
overview is displayed.

Basic adjustment

Display
Diagnostics
Service
Info

2

Confirm the menu "Basic adjustment" with [OK].

Application

Level

3

Confirm the menu item "Application" with [OK].

Warning:
Note the warning: "Output can change".

4

Select with [->] "OK" and confirm with [OK].

5

Select the requested application in the selection list, for example
"F

low" and confirm with [OK].

Introduction

Application

Differential pressure transmitter DPT10 - metal measuring diaphragm • Foundation Fieldbus

45