beautypg.com

WIKA DPT-10 User Manual

Page 20

background image

à Mount DPT10 below the lower measurement connection so that

the effective pressure lines are always filled with liquid

à Connect minus side always above the max. level
à For measurements in products with solid content such as e.g. dirty

liquids, the installation of separators and drain valves is
recommended to enable collection and removal of debris and
sediment.

+

min.

max.

1

3

4

3

4

5

1

2

Fig. 15: Measurement setup, level measurement in closed vessel

1

Blocking valves

2

DPT10

3

Precipitator

4

Drain valves

5

3

-fold valve block

à Mount DPT10 directly to the vessel

à Connect minus side always above the max. level
à For measurements in products with solid content such as e.g. dirty

liquids, the installation of separators and drain valves is
recommended to enable collection and removal of debris and
sediment.

In closed vessels with
effective pressure lines

In closed vessels with
unilateral pressure
transmitter

20

Differential pressure transmitter DPT10 - metal measuring diaphragm • Foundation Fieldbus

4 Mounting

37246

-EN

-100120