WIKA DPT-10 User Manual
Page 20
à Mount DPT10 below the lower measurement connection so that
the effective pressure lines are always filled with liquid
à Connect minus side always above the max. level
à For measurements in products with solid content such as e.g. dirty
liquids, the installation of separators and drain valves is
recommended to enable collection and removal of debris and
sediment.
+
–
min.
max.
1
3
4
3
4
5
1
2
Fig. 15: Measurement setup, level measurement in closed vessel
1
Blocking valves
2
DPT10
3
Precipitator
4
Drain valves
5
3
-fold valve block
à Mount DPT10 directly to the vessel
à Connect minus side always above the max. level
à For measurements in products with solid content such as e.g. dirty
liquids, the installation of separators and drain valves is
recommended to enable collection and removal of debris and
sediment.
In closed vessels with
effective pressure lines
In closed vessels with
unilateral pressure
transmitter
20
Differential pressure transmitter DPT10 - metal measuring diaphragm • Foundation Fieldbus
4 Mounting
37246
-EN
-100120