.3 Measurement setup flow
à Mount DPT10 above the measurement loop so that condensate
can drain off in the process cable.
+
–
1
2
4
3
Fig. 10: Measurement setup, flow measurement in gases
1
DPT10
2
3
-fold valve block
3
Blocking valves
4
Orifice or impact pressure probe
à Mount DPT10 below the measurement loop
à Mount condensate vessels at the same height with the discharge
socket and at the same distance to DPT10
à For measurements in products with solid content such as e.g. dirty
liquids, the installation of separators and drain valves is
recommended to enable collection and removal of debris and
sediment.
à Fill the effective pressure lines to the height of the condensate
vessels before setup
In gases
In vapours
16
Differential pressure transmitter DPT10 - metal measuring diaphragm • Foundation Fieldbus
4 Mounting
37246
-EN
-100120
- 890.09.2190 (44 pages)
- A-10 (96 pages)
- A2G-50 (52 pages)
- A2G-55 (36 pages)
- AC-1 (88 pages)
- C-2 (24 pages)
- D-10-7 (112 pages)
- D-20-9 (51 pages)
- D-20-9 (35 pages)
- DG-10 (112 pages)
- DP-10 (44 pages)
- DPT-10 (96 pages)
- GCS-1 (76 pages)
- HP-2 (84 pages)
- IL-10 (31 pages)
- IPT-10 (28 pages)
- IPT-10 (36 pages)
- IPT-10 (56 pages)
- IPT-10 (48 pages)
- IS-20-F (7 pages)
- IS-20-F (43 pages)
- IS-20-H (7 pages)
- UT-10 (42 pages)
- UT-10 (52 pages)
- IUT-10 (78 pages)
- LH-10 (60 pages)
- LH-20 (60 pages)
- LS-10 (60 pages)
- MG-1 (92 pages)
- MH-1 (11 pages)
- MH-2 (9 pages)
- MHC-1 (84 pages)
- N-10 (35 pages)
- O-10 (108 pages)
- OT-1 (60 pages)
- P-30 (92 pages)
- PSA-31 (124 pages)
- PSD-30 (128 pages)
- R-1 (92 pages)
- S-10 (35 pages)
- S-11 (102 pages)
- S-20 (52 pages)
- S-20 (96 pages)
- SL-1 (21 pages)