8. Faults

In the event of any faults, first check whether the pressure transmitter is mounted correctly, mechanically

and electrically.

8. Faults

Faults

Causes

Measures

No output signal

Cable break

Check the continuity

Deviating zero point signal

Overpressure limit exceeded

Observe the permissible overpressure

limit

Deviating zero point signal

Too high/low working temperature

Observe the permissible temperatures

Constant output signal upon

change in pressure

Mechanical overload caused by

overpressure

Replace instrument; if it fails repeatedly,

contact the manufacturer

Signal span varies

EMC interference sources in the

environment; for example, frequency

converter

Shield instrument; cable shield; remove

source of interference

Signal span varies/inaccurate

Too high/low working temperature

Observe the permissible temperatures

Signal span drops/too small

Mechanical overload caused by

overpressure

Replace instrument; if it fails repeatedly,

contact the manufacturer

If complaint is unjustified, we will charge you the complaint processing fees.

CAUTION!

If faults cannot be eliminated by means of the measures listed above, shut down the

pressure transmitter immediately, and ensure that pressure and/or signal are no longer

present, and secure the instrument from being put back into operation inadvertently. In this

case, contact the manufacturer. If a return is needed, follow the instructions given in chapter

9.2 "Return".