Faults, Gb 8. faults – WIKA A-10 User Manual
Page 22

22
WIKA operating instructions pressure transmitter model A-10
11218720.10 01/2012 GB/D/F/E
GB
8. Faults
In the event of any faults, first check whether the pressure transmitter is mounted correctly, mechanically
and electrically.
8. Faults
Faults
Causes
Measures
No output signal
Cable break
Check the continuity
Deviating zero point signal
Overpressure limit exceeded
Observe the permissible overpressure
limit
Deviating zero point signal
Too high/low working temperature
Observe the permissible temperatures
Constant output signal upon
change in pressure
Mechanical overload caused by
overpressure
Replace instrument; if it fails repeatedly,
contact the manufacturer
Signal span varies
EMC interference sources in the
environment; for example, frequency
converter
Shield instrument; cable shield; remove
source of interference
Signal span varies/inaccurate
Too high/low working temperature
Observe the permissible temperatures
Signal span drops/too small
Mechanical overload caused by
overpressure
Replace instrument; if it fails repeatedly,
contact the manufacturer
If complaint is unjustified, we will charge you the complaint processing fees.
CAUTION!
If faults cannot be eliminated by means of the measures listed above, shut down the
pressure transmitter immediately, and ensure that pressure and/or signal are no longer
present, and secure the instrument from being put back into operation inadvertently. In this
case, contact the manufacturer. If a return is needed, follow the instructions given in chapter
9.2 "Return".