11. TECHNICAL DATA


Housing:
self extinguishing ABS
Case:
face 100x64 mm; depth 45.5mm
Mounting: J-box or wall-mount in suitable enclosure
Frontal protection: IP65
Connections: ¼” fast-on for power, 1/8” fast-on for probes and Digital Inputs
Power supply: 120Vac

±

10%, optional 230Vac

±

10% MAX 15A

Power absorption: 4VA max.
Ambient Temperature: 32-131°F (0-55°C)
Display
: 3 digits, red LED, 14,2 mm high.
Inputs: 1 NTC probe
Digital inputs: 2 free voltages
Relay outputs: Relay Contacts

Light: relay SPST 15A, 120Vac;
Alarm: relay SPST 8A, 120Vac

Other output: alarm buzzer
Data storing: on the non-volatile memory (EEPROM).
Measuring and regulation range:

NTC probe: -40÷110°C (-58÷230°F)

Resolution: 1 °F
Accuracy : ±1 °F

12. CONNECTIONS

Power supply: 120Vac +/- 10% 15A MAX current