XWA11V Walk-in Alarm / Door / Alarm / Light Unit Operation Manual
In Normal Operation the Indicator will display the temperature.
36° F
CHECK ALARM SETPOINTS
(Cooler
HA
=
50°F
,
LA
=
30°F
/ Freezer
HA
=
30°F
,
LA
=
-20°F
)
To SEE the HIGH Alarm Set Point Press and release the
Key, It will display the High
Set Point for 5 seconds. The Temp alarm will go ON if the temp exceeds the Set Point after
15 minutes. The display will read
HA
alternating with the Temp.
To SEE the LOW Alarm Set Point Press and release the
Key it will display the Low
Set Point for 5 seconds. The Temp alarm will go ON if the temp exceeds the Set Point after
15 minutes.
LA
, alternating with the Temp.
CHANGE ALARM SETPOINTS
1. To Change the HIGH Alarm Set Point Press BOTH the
for 7 seconds
and the LED above the
will blink.
2. Release and scroll UP
to adjust the Set Point up, or Scroll DOWN
to adjust
the Set point down.
3. Press
to confirm the change.
4. For Low Set Point repeat the procedure with the
LIGHT OPERATION
Press the light switch
to turn ON the inside light; it will automatically go OFF after 15
minutes.
DOOR SWITCH
If the door switch is used opening the door will automatically turn the light
ON, and will
automatically go OFF after 15 minutes.
If the Door is left open longer than 15 minutes the DOOR Alarm will go off,
dA
alternating
with the temperature reading.
ALARM SIGNALS