QUICK SHEET

XWA11V Walk-in Alarm / Door / Alarm / Light Unit Operation Manual

In Normal Operation the Indicator will display the temperature.

36° F

CHECK ALARM SETPOINTS

(Cooler

HA

=

50°F

,

LA

=

30°F

/ Freezer

HA

=

30°F

,

LA

=

-20°F

)

To SEE the HIGH Alarm Set Point Press and release the

Key, It will display the High

Set Point for 5 seconds. The Temp alarm will go ON if the temp exceeds the Set Point after

15 minutes. The display will read

HA

alternating with the Temp.

To SEE the LOW Alarm Set Point Press and release the

Key it will display the Low

Set Point for 5 seconds. The Temp alarm will go ON if the temp exceeds the Set Point after

15 minutes.

LA

, alternating with the Temp.


CHANGE ALARM SETPOINTS

1. To Change the HIGH Alarm Set Point Press BOTH the

for 7 seconds

and the LED above the

will blink.

2. Release and scroll UP

to adjust the Set Point up, or Scroll DOWN

to adjust

the Set point down.

3. Press

to confirm the change.

4. For Low Set Point repeat the procedure with the


LIGHT OPERATION

Press the light switch

to turn ON the inside light; it will automatically go OFF after 15

minutes.

DOOR SWITCH

If the door switch is used opening the door will automatically turn the light

ON, and will

automatically go OFF after 15 minutes.

If the Door is left open longer than 15 minutes the DOOR Alarm will go off,

dA

alternating

with the temperature reading.