beautypg.com

Prior to start up - required ability, Operating instructions – A.O. Smith 400A User Manual

Page 25

background image

5

DO NOT USE THIS HEATER IF ANY PART HAS BEEN UNDER

WATER. IMMEDIATELY CALL A QUALIFIED SERVICE TECHNICIAN

TO INSPECT THE HEATER AND TO REPLACE ANY PART OF THE

CONTROL SYSTEM AND ANY GAS CONTROL WHICH HAS BEEN

UNDER WATER.

LIGHT THE UNIT IN ACCORDANCE WITH THE OPERATING

INSTRUCTIONS LABEL ATTACHED TO THE HEATER.

THESE INSTRUCTIONS ARE REPEATED IN THE LIGHTING AND

OPERATING LABEL ILLUSTRATION IN THIS MANUAL.

ADJUSTMENT PROCEDURE - INITIAL START-UP

A minimum dynamic gas supply pressure of 5.2" W.C. (1.29 kPa)

for Natural Gas and 11" W.C. (2.74 kPa) for LP Gas is required

before making any adjustment to the gas control pressure regulator

Attempts to adjust the regulator during periods of low gas supply

pressure could result in overfiring of the heater when the gas supply

pressure returns to normal.

1. Check gas line pressure with a manometer, adjust the gas supply

line pressure per table 4.

2. Check manifold pressure (see Table 4) using a pressure gauge

(manometer) connected to the manifold pressure tap on the gas

control valve, (Figure 15).

If full rate adjustment is required, remove cover screw from top of

the gas control valve, (Figure 15).

Using a small screwdriver, turn adjusting screw clockwise to

increase or counterclockwise

to decrease gas pressure to

obtain 4.0" W.C. (0.996 kPa) for Natural Gas and 10" W.C. (2.49

kPa) for LP gas.

3. Cycle the burner on and off several times to check its operation.

4. Check the operation of the limit and operating controls.

5. Check the vent system seams and joints and ensure that there

is no discharge of flue products into the room.

6. Check the input rate:

For appliance installation locations with elevations above 10,000

feet (3,048 m) refer to HIGH ALTITUDE INSTALLATIONS section

of this manual.

a. Attach a pressure gauge (manometer) to the manifold pressure

tap (Figure 16) and refer to Table 4 for correct pressure.

b. Use this formula to “clock” the meter. Be sure other gas

consuming appliances are not operating during this interval.

3600

T

T = Time in seconds to burn 1 cubic foot of gas. (With a stopwatch

read the gas meter and measure the amount of time required for

the heater to consume 1 cubic foot of gas.)

H = Heating value of gas (in Btu’s per cubic foot of gas).

Btuh = Actual heater input rate, in Btuh.

EXAMPLE: (Using BTH-300 heater)

T = 12.6 seconds

H = 050 Btu/ft.

3

BTUH = ?

For high altitude installations, compare result to the derated input

required for the elevation at the installation location.

Should it be necessary to adjust the gas pressure to the burner,

to obtain the full input rate, the steps below should be followed:

PRIOR TO START UP - REQUIRED ABILITY

INSTALLATION OR SERVICE OF THIS WATER HEATER REQUIRES

ABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMAN IN

THE FIELD INVOLVED. PLUMBING, AIR SUPPLY, VENTING, GAS

SUPPLY AND ELECTRICAL WORK ARE REQUIRED.

Before attempting start-up, thoroughly study and familiarize yourself

with the exact sequence of operation and all other details on the

specific heater being used.

The power burner is equipped with an ignition system which

automatically sequences prepurge and ignition, senses and

ignites main burner flame and sequences burner operation.

Heater is equipped with an ignition control which locks out after

three unsuccessful ignition attempts. Familiarize yourself with the

sequence of operation of this unit prior to start-up.

Be certain that the water heater is full of water, that air is purged

from all lines, there are no leaks (gas and water), and all inlet water

lines are open.

The following test equipment should be on hand (all test

equipment must be acclimated to ambient temperature before

calibration and use.)

– Two U-tube manometers or calibration 0-10" W.C. (0-2.5Kpa) and

0-35" W.C. (0-8.7Kpa) pressure gauges.

• Attach a gas pressure gauge or manometer to the upstream side

of main gas cock and a gas pressure gauge or manometer to the

manifold pressure tap.

• You are now ready to begin the burner start-up procedure.

OPERATING INSTRUCTIONS

IMPORTANT

IT IS RECOMMENDED THAT A QUALIFIED SERVICE TECHNICIAN

PERFORM THE INITIAL FIRING OF THE HEATER. AT THIS TIME THE

USER SHOULD ASK THE TECHNICIAN ANY QUESTIONS IN REGARD

TO THE OPERATION AND MAINTENANCE OF THE UNIT.

CAUTION

BEFORE PROCEEDING WITH THE OPERATION OF THE UNIT,

MAKE SURE HEATER AND SYSTEM ARE FILLED WITH WATER

AND ALL AIR IS EXPELLED FROM HEATER AND PIPING.

NEVER OPERATE THE HEATER WITHOUT FIRST BEING

CERTAIN IT IS FILLED WITH WATER AND A TEMPERATURE AND

A PRESSURE RELIEF VALVE IS INSTALLED IN THE RELIEF VALVE

OPENING OF THE HEATER. DO NOT ATTEMPT TO OPERATE

HEATER WITH COLD WATER INLET VALVE CLOSED.

FILLING:

1. Close the heater drain valve.

2. Open a nearby hot water faucet to permit the air in the system

to escape.

3. Fully open the cold water inlet pipe valve allowing the heater

and piping to be filled.

4. Close the hot water faucet as water starts to flow.

5. The heater is ready to be operated.

THE MAIN MANUAL GAS SHUTOFF VALVE MUST HAVE BEEN CLOSED

FOR AT LEAST FIVE (5) MINUTES. THIS WAITING PERIOD IS AN

IMPORTANT SAFETY STEP. ITS PURPOSE IS TO PERMIT GAS THAT

MIGHT HAVE ACCUMULATED IN THE COMBUSTION CHAMBER TO

CLEAR. IF YOU DETECT GAS AT THE END OF THIS PERIOD, DO NOT

PROCEED WITH LIGHTING. RECOGNIZE THAT GAS ODOR, EVEN IF

IT SEEMS WEAK, MAY INDICATE THE PRESENCE OF ACCUMULATED

GAS SOMEPLACE IN THE AREA WITH A RISK OF FIRE OR EXPLOSION.

SEE THE FRONT PAGE FOR STEPS TO BE TAKEN.

X H = Btuh

3600

X

1050 = 300,000 Btuh (87.9 kW)

12.6

This manual is related to the following products: