codes or contact the water supplier or local plumbing inspector on

how to control this situation.

WATER (POTABLE) HEATING AND SPACE HEATING

1. All piping components connected to this unit for space heating

applications shall be suitable for use with potable water.

2. Toxic chemicals, such as those used for boiler treatment, shall

NEVER be introduced into this system.

3. This unit may never be connected to any existing heating system

or component(s) previously used with non-potable water heating

appliance.

4. When the system requires water for space heating at temperatures

higher than required for domestic water purposes, a tempering

valve must be installed. Please refer to installation diagrams

on pages 30 through 35 in back of manual for suggested piping

arrangements.

HEATER WIRING

IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE

APPLIANCE MUST BE REPLACED, IT MUST BE REPLACED

WITH 105°C OR ITS EQUIVALENT, EXCEPT IN THE BURNER

HOUSING. IN THIS CASE USE 200°C WIRE.

THE COMPUTER CONTROL REQUIRES A SOURCE OF STABLE

CLEAN ELECTRICITY FOR PROPER OPERATION. INSTALLING

THE HEATER ON A BRANCH CIRCUIT THAT HAS ELECTRONIC

NOISE, IS SUBJECT TO FLUCTUATIONS IN VOLTAGE LEVEL

OR HAS AN APPLIANCE WHICH GENERATES EMF OF

RFI INTERFERENCE CAN CAUSE THE CONTROLLER TO

MALFUNCTION. A HIGH QUALITY POWER CONDITIONER

MUST BE INSTALLED IF THE ABOVE CONDITIONS EXIST.

MALFUNCTIONS CAUSED BY A POOR ELECTRICAL SUPPLY

ARE NOT COVERED UNDER YOUR WARRANTY.

The controller is wired to the heater as shown in figures 15 & 16. The

model and rating plate provides the electrical information needed to

size the complete heater branch supply.

All electrical work must be installed in accordance with the National

Electrical Code, NFPA 70 or the Canadian Electrical Code, CSA

C22.1 and local requirements.

When installed, the appliance must be electrically grounded in

accordance with local codes or, in the absence of local codes,

with the National Electrical Code, ANSI/NFPA 70 or the Canadian

Electrical Code, CSA C22.1.

DO NOT ENERGIZE THE BRANCH CIRCUIT BEFORE THE

HEATER TANK IS FILLED WITH WATER.

NOTE: This controller is Polarity Sensitive. If the Hot and Neutral

Supply Voltage is reversed, the controller will not sense flame. Verify

polarity before connecting the unit.