Alarms and Events

Alarms

Description

Action

23. Main inverter failure

Temperature of main inverter, too
high or inverter fuse blown

Check fan, check for airflow
obstructions, check for overload,
check fuse

24. High temperature of delta

inverter

Temperature of delta inverter, too
high

Check fan, check for airflow
obstructions, check for overload

25. Low DC shutdown

Battery discharged to minimum
permissible level

Ensure battery recharging

26. Low DC warning

Battery nearly discharged

Save your data now

27. Mains momentarily outside

tolerance

Short disturbances on mains
supply (1 ms transients)

28. Mains outside tolerance

Mains input voltage R.M.S. value
outside tolerance

29. Mains frequency outside

tolerance

Mains input frequency outside
tolerance

30. Bypass momentarily outside

tolerance

Short disturbances on bypass
voltage

31. Bypass outside tolerance

Bypass input voltage outside
tolerance

32. Bypass frequency outside

tolerance

Bypass input frequency outside
tolerance

33. Output momentarily outside

tolerance

Short disturbance on output
voltage (inrush current)

If message reappears -
call for assistance

34. Output outside tolerance

Output voltage outside tolerance

Call for assistance

35. Output frequency outside

tolerance

Output frequency outside
tolerance

Call for assistance

36. High battery temperature

Battery ambient temperature too
high

Check system ambient
temperature, check fan, check for
airflow obstructions

37. Battery weak

Battery capacity below 75% or
battery MCCB/fuse switched off

Test battery capacity

38. Battery defective

Insufficient battery capacity or
battery MCCB/fuse switched off

Call for assistance

39. System locked in operation

mode

UPS has made 10 attempts within
1 minute to switch from bypass to
battery operation, or “High DC
warning” has appeared 10-20
times within 1 minute

Unlock.
If message reappears -
call for assistance

40. RAM1 memory write error

UPS fault

Call for assistance

41. Memory write error

UPS fault

Call for assistance

42. Communication to VQ bypass

lost

UPS fault

Call for assistance

43. Communication to VQ output

lost

UPS fault

Call for assistance

44. Communication to DMU lost

UPS fault

Call for assistance

45. Communication to controller

lost

UPS fault.
Display will show invalid UPS data