Stop/Start UPS and Operating the External Service Bypass

990-4058

User Guide APC Silcon 480kW 400V UPS

13

Action

Steps 1-4 apply to all the parallel systems. Note that this will switch all systems
into bypass operation

1. Press

on the keyboard

2. Press

or on the keyboard until

3. Press

on the keyboard

4. Press

on the keyboard

All systems switch to bypass operation

Do not switch off any of the UPS systems
until steps 5-8 have been completed

5. Check light indication on the bypass panel

6. Set the external bypass switch (Q003) to position 1

7. Set the output switch (Q004) to position 0

8. Set all output switches (Q002) to position 0

9. Open the front door of any one system and press the green

ON and the red OFF button simultaneously
The acoustic alarm sounds for 30 secs*
Repeat for (all) other system(s)

10. Set all input switches (Q001) to position 0

The red alarm LED below the display lights up and
the acoustic alarm sounds for 30 secs*

*Reset the acoustic alarm by pressing the key.

Display shows

Bypass operation

: NO

Bypass operation

**System OFF**

Bypass operation

: YES

Lamp indication on
Bypass Panel

Green light (H003)
above the bypass switch
handle (Q003) lights up

Green light (H004)
above the output switch
handle (Q004) and green
lights (H002) above the
output switch handles
(Q002) light up

H003 switches off
H002 and H004 still on

H002 and H004 still on

Display shows