beautypg.com

Alarms and events, 3 possible alarms – American Power Conversion 480kW400V User Manual

Page 25

background image

Alarms and Events

990-4058

User Guide APC Silcon 480kW 400V UPS

25

5.3

Possible Alarms

Alarms

Description

Action

1. Peak current limiter active

Peak current limiter activated and
UPS switched to bypass operation.
System overload

Check for blown fuses in
installation

2. Bypass power supply fault

Fault in redundant PSU for bypass.
UPS still 100% able to operate in
all modes.

Call for assistance

3. Delta current limiter active

Input current limiter activated and
UPS switched to bypass operation

Check for overload.
If message is repetitive -
call for assistance

4. Faulty fan

Blocked or faulty fan

Remove blocking or replace fan

5. High DC warning

Switching off big output load

If alarm is repeated, reduce load
change

6. High DC shutdown

UPS fault

Call for assistance

7. Off-button activated

Off button or emergency power
shut down activated

8. Synchronization error

UPS unable to synchronize with
input frequency

Check if phase rotation of mains
input voltage is correct. If OK, call
for assistance

9. Inverter voltage error

Inverter average voltage outside
limits (normal message during
system start-up/switch-off

10. Parallel synchronization

error

Parallel UPS unable to
synchronize

Check external parallel cables -
call for assistance

11. Inverter current limiter active

Inverter overload

Reduce UPS output load

12. Overload. Load exceeding

100%

UPS overload

Reduce UPS output load

13. Second power supply fault

UPS fault
(only systems > 160kW)

Call for assistance

14. Internal power supply fault

UPS fault. Only bypass operation
possible

Call for assistance

15. Battery MCCB is off

Battery MCCB/fuse not closed or
released

Close MCCB / insert new fuse. If
released again -
call for assistance.

16. **Q004 off**

Output switch position for UPS in
parallel

17. **Q003 off**

External bypass switch position

18. **Q002 off**

UPS output switch position

19. **Q001 off**

UPS input switch position

20. High temperature of isolation

transformer

Temperature of isolation input/
output transformer, too high

Check fan, check for airflow
obstructions, check for overload

21. High temperature of main static

switch

Temperature of static input switch,
too high

Check fan, check for airflow
obstructions, check for overload

22. High temperature of bypass

static switch

Temperature of static bypass
switch, too high

Check fan, check for airflow
obstructions, check for overload