American Power Conversion 480kW400V User Manual

Page 11

background image

Stop/Start UPS and Operating the External Service Bypass

990-4058

User Guide APC Silcon 480kW 400V UPS

11

NOTICE!

If battery has been disconnected, please refer to section 2.4.1 UPS start-up.

Action

1. Set the input switch (Q001) to position 1

2. Wait 5 sec. Open the front door of the UPS and

press the green ON key

3. Press on the keyboard

4. Press or on the keyboard until

5. Press on the keyboard

6. Press on the keyboard

7. Check light indication on the bypass panel

8. Set the output switch (Q002) to position 1

9. Set the bypass switch (Q003) to position 0

10. Press on the keyboard

11. Press or

on the keyboard until

12. Press on the keyboard

13. Press on the keyboard

14. Press on the keyboard

15. Press on the keyboard

Display shows

Bypass operation

: NO

Bypass operation

: NO

Normal operation

load power 0%

Normal operation

load power 0%

**System OFF**

Bypass operation

: YES

Bypass operation

: YES

Lamp indication on
Bypass Panel

Green light (H002)
above the output switch
handle (Q002) lights up

Green light (H003)
above the bypass switch
handle (Q003) lights up

Only the light (H003)
above the bypass switch
handle (Q003) is now on

Display shows

All lights on the bypass
panel switched off