Stop/Start UPS and Operating the External Service Bypass

990-4058

User Guide APC Silcon 480kW 400V UPS

15

Action

1. Check that the output switch (Q004) is set to position 0

2. Check that all output switches (Q002) are set to position 1

3. Set input switches (Q001) to position 1

4. Wait 10 secs.

Open the UPS front door and
press the green ON button on all systems

5. Press

on the keyboard

6. Press

or on the keyboard until

7. Press

on the keyboard

8. Press

on the keyboard

All systems switch to bypass operation

Note!
If Q002s are in position 0 off, only programmed
systems will switch to bypass

9. Set the output switch (Q004) to position 1

10. Turn the bypass switch (Q003) to position 0

The following can be carried out on any UPS

11. Press

on the keyboard

12. Press

or

on the keyboard until

13. Press

on the keyboard

14. Press

on the keyboard

All the systems will transfer to normal
operation

Display shows

Bypass operation

: NO

Bypass operation

: NO

Bypass operation

: YES

Bypass operation

**System OFF**

Bypass operation

: YES

Lamp indication on
Bypass Panel

H002 and H004 light up

Green light (H003) above
bypass switch lights up

The green lamps (H002)
and (H004) are switched
off, but (H003) is lit
until normal operation.

Display shows

No lamps on the bypass
panel are lit

Normal operation

load power 0%

Normal operation

load power 0%