38 Cyclades PM IPDU Installer/Administrator/User Guide
Interface Pinouts
Table A.2: PM42 IPDU Specifications
Characteristics
Electrical
Input Voltage
Three phases, phase to phase 208 VAC
Max Input Current
24A
Max Output Current Total
16A on any single bank (XY, YZ or XZ)
-or-
13.8A evenly distributed on each bank (XY, YZ or XZ)
NOTE: Maximum allowed current in any bank is limited to 16A
although the maximum of 24A input current per phase must not be
exceeded. If equal loads are provided to all banks then, in order to
have this maximum input current of 24A, the maximum allowed
current per bank will have to be decreased to 13.8A.
Max Output Current Each Outlet
42 - IEC320-C13: 12A at 208 VAC (42 places)
Environmental
Operating Temperature
0-50ºC
Mechanical
Weight
10.89 kg
Physical Dimensions (W x D x H)
2.2 x 2.5 x 72.0 in
Table A.3: Pinouts for IN and OUT RS-232 Serial Ports
Signal
Name/Function
I/O
IN Pin
OUT Pin
RTS
Request to Send
(O)
5
1
DTR
Data Terminal Ready
(O)
7
2
TxD
Transmit Data
(O)
6
3
Gnd
Ground
N/A
4
4
CTS
Clear to Send
(I)
1
5
RxD
Receive Data
(I)
3
6
DCD
Data Carrier Detect
(I)
2
7