3 — PROGRAMMABLE PARAMETERS:
Hourmeters
HOURMETER TYPE
The Spyglass gauge displays hourmeter data for 5 seconds each time the key-
switch is turned on. The hourmeter type parameter defines whether the total
hourmeter or traction hourmeter data will be displayed. When this parameter
is programmed On, the total hourmeter is displayed; when programmed Off,
the traction hourmeter is displayed.
PUMP METER
The pump meter parameter, when programmed On, configures the Fault
Output 1 line (at Pin 2) to function as an input to measure the hours a pump
is running. The pump is considered to be running when Pin 2 is at the battery
voltage. When the pump meter parameter is programmed On, the traction
hourmeter serves as a combination traction/pump hourmeter, and all the above
“
TRAC
” hourmeter parameters apply to both traction hours and pump hours.
The traction/pump hourmeter counts the hours when a direction is selected
and the hours when the pump is running.
Other Hourmeter Parameters
- BCT-6200-6CA BCT-6000-6SA BCT-6000-6CA BCT-6250-6SA BCT-6250-6CA BC-620-6SA BC-620-6CA BC-600-6SA BC-600-6CA BC-625-6SA BC-625-6CA BC-620-4SA BC-620-4CA BC-600-4SA BC-600-4CA BC-625-4SA BC-625-4CA SCT-7750-6AC SCT-7750-6CA MV-520-6SA PCT-3510-6SA ST PCT-3510-6CA ST PCT-3510-6SA HB PCT-3510-6CA HB PCT-3500-6SA PCT-3500-6CA PC-300-6SA PC-300-6CA PC-325-4SA PC-325-4CA PC-300-4SA PC-300-4CA PMT-5000-6CA PMT-5000-6SA PMT-4500-6SA PMT-4500-6CA SC-775-6AC SC-775-6SA SC-775-6CA SC-750-4SA SC-750-4CA