3 — PROGRAMMABLE PARAMETERS:
Hourmeters
Once the preset values have been loaded, the Set Total Hours parameter
should be programmed Off.
SET TRAC HRS
The set traction hours parameter is used to apply preset high, middle, and
low values to the traction hourmeter. First, adjust the preset values as desired
for the traction hourmeter. Then, program the Set Traction Hours parameter
On, which automatically loads the preset values. Once they have been loaded,
the Set Traction Hours parameter should be programmed Off.
SRVC TOTL HRS
The total service hours parameter is used to set the timer for the next sched-
uled overall maintenance. The service interval can be up to 5,000 hours. The
total service timer is adjustable between 0.0 and 50.0, in 0.5 increments, with
25.0 being equivalent to 2,500 hours (25.0 × 100).
Setting the parameter to 0 means that the timer will never expire—i.e.,
there will be no overall maintenance reminder.
SRVC TRAC HRS
The traction service hours parameter is used to set the timer for the next
scheduled traction motor maintenance. The service interval can be up to 5,000
hours. The traction service timer is adjustable between 0.0 and 50.0, in 0.5
increments, with 25.0 being equivalent to 2,500 hours (25.0 × 100).
Setting the parameter to 0 means that the timer will never expire—i.e.,
there will be no motor maintenance reminder.
DIS TOTL HRS
The total disable hours parameter is used to set the total disable timer; it can
be adjusted between 0 and 250 hours, in 1 hour increments. If the total disable
timer expires, the traction fault speed goes into effect.
Setting the parameter to 0 means that the total disable timer will never
expire and therefore never invoke the traction fault speed.
DIS TRAC HRS
The traction disable hours parameter is used to set the traction disable timer;
it can be adjusted between 0 and 250 hours, in 1 hour increments. If the trac-
tion disable timer expires, the traction fault speed goes into effect.
Hourmeter Service Timer Setting
Hourmeter Disable Timer Setting
- BCT-6200-6CA BCT-6000-6SA BCT-6000-6CA BCT-6250-6SA BCT-6250-6CA BC-620-6SA BC-620-6CA BC-600-6SA BC-600-6CA BC-625-6SA BC-625-6CA BC-620-4SA BC-620-4CA BC-600-4SA BC-600-4CA BC-625-4SA BC-625-4CA SCT-7750-6AC SCT-7750-6CA MV-520-6SA PCT-3510-6SA ST PCT-3510-6CA ST PCT-3510-6SA HB PCT-3510-6CA HB PCT-3500-6SA PCT-3500-6CA PC-300-6SA PC-300-6CA PC-325-4SA PC-325-4CA PC-300-4SA PC-300-4CA PMT-5000-6CA PMT-5000-6SA PMT-4500-6SA PMT-4500-6CA SC-775-6AC SC-775-6SA SC-775-6CA SC-750-4SA SC-750-4CA