Wiring: throttle – Wesley BCT-6200-6SA User Manual
Page 17
Curtis 1243
GEN
2 Manual,
Rev. B
9
2 — INSTALLATION & WIRING:
Throttle
WIRING: Throttle
Wiring for various throttles is described below. They are categorized as Type 1,
2, 3, and 4 throttles in the program menu of the handheld programmer. Note:
In the text, throttles are identified by their nominal range and not by their
actual active range.
Appropriate throttles for use with the 1243
GEN
2 controller include two-
wire 5kΩ–0 throttles (“Type 1”); 0–5V throttles, current source throttles,
three-wire potentiometer throttles, and electronic throttles wired for single-
ended operation (all “Type 2”); two-wire 0–5kΩ throttles (“Type 3”), and
0–5V and three-wire potentiometer throttles wired for wigwag operation (“Type
4”). The operating specifications for these throttle types are summarized in Table
1. Refer to Section 3: Programmable Parameters, for information on the effects
of the Throttle Deadband and Throttle Max parameters on the minimum and
maximum throttle thresholds.
If the throttle you are planning to use is not covered, contact the Curtis
office nearest you.
Table 1 THROTTLE WIPER INPUT THRESHOLD VALUES
MAXIMUM
THROTTLE
HPD
THROTTLE
MINIMUM
THROTTLE
THROTTLE
DEADBAND
(25% throttle
MAX
THROTTLE
TYPE
PARAMETER
FAULT
(0% speed request)
active range)
(100% modulation)
FAULT
1
(5kΩ–0)
Wiper Voltage
5.00 V
3.80 V
2.70 V
0.20 V
0.06 V
Wiper Resistance
7.50 kΩ
5.50 kΩ
3.85 kΩ
0 kΩ
—
2
(0–5V)
Wiper Voltage
0.06 V
0.20 V
1.50 V
5.00 V
5.80 V
Wiper Resistance
—
—
—
—
—
3
(0–5kΩ)
Wiper Voltage
0.06 V
0.20 V
1.30 V
3.80 V
5.00 V
Wiper Resistance
—
0 kΩ
1.65 kΩ
5.50 kΩ
7.50 kΩ
4
(0–5V)
Wiper Voltage
0.50 V
2.50 V (fwd)
*
3.10 V (fwd)
4.40 V (fwd)
4.50 V
2.50 V (rev)
*
1.90 V (rev)
0.60 V (rev)
Wiper Resistance
—
—
—
—
—
Notes: The Throttle Deadband and Throttle Max thresholds are valid for nominal 5kΩ
potentiometers or 5V sources with the default Throttle Deadband and Throttle
Max parameter settings of 0% and 100% respectively. These threshold values
will change with variations in the Throttle Deadband and Throttle Max parameter
settings.
The HPD thresholds are 25% of the active throttle range and therefore depen-
dent on the programmed Throttle Deadband and Throttle Max settings (which
define the active range).
The wiper voltage is measured with respect to B-.
The wiper resistance is measured from pot low to pot wiper. The potentiometer
must be disconnected from the controller when making this measurement.
*
With a 0% Throttle Deadband setting, there is no neutral point
on a Type 4 throttle. A Throttle Deadband setting of at least 8%
is recommended for Type 4 throttles.
- BCT-6200-6CA BCT-6000-6SA BCT-6000-6CA BCT-6250-6SA BCT-6250-6CA BC-620-6SA BC-620-6CA BC-600-6SA BC-600-6CA BC-625-6SA BC-625-6CA BC-620-4SA BC-620-4CA BC-600-4SA BC-600-4CA BC-625-4SA BC-625-4CA SCT-7750-6AC SCT-7750-6CA MV-520-6SA PCT-3510-6SA ST PCT-3510-6CA ST PCT-3510-6SA HB PCT-3510-6CA HB PCT-3500-6SA PCT-3500-6CA PC-300-6SA PC-300-6CA PC-325-4SA PC-325-4CA PC-300-4SA PC-300-4CA PMT-5000-6CA PMT-5000-6SA PMT-4500-6SA PMT-4500-6CA SC-775-6AC SC-775-6SA SC-775-6CA SC-750-4SA SC-750-4CA