Hourmeter parameters – Wesley BCT-6200-6SA User Manual
Page 53
Curtis 1243
GEN
2 Manual,
Rev. B
45
3 — PROGRAMMABLE PARAMETERS:
Hourmeters
Two individual hourmeters are built into the 1243
GEN
2 controller, each with non-
volatile memory:
• a total hourmeter, that measures the total operating time (KSI on-time), and
• a traction hourmeter, that measures the time that a direction is selected.
Each hourmeter has a corresponding service timer and disable timer. Hourmeter
information is viewable via the programmer or the Spyglass display.
For each hourmeter, the service timer is used to set the time before scheduled
maintenance is due. When the set service time expires, the service warning fault
occurs and the disable timer starts. If the programmed disable time expires before
the scheduled maintenance is performed, the controller defaults to the programmed
traction fault speed.
The 1243
GEN
2 controller is shipped from the factory with each of its two hourmeters
preset to 0. If the controller is being installed in a new vehicle, these presets do not
need to be adjusted. If the controller is being installed in a “used” vehicle, however,
it may be desirable to transfer the existing hourmeter values to the new controller.
To do this, the existing hourmeter values must be entered as follows.
Each meter records time to 999999.9 hours (114 years), and will roll over
to 000000.0 if this is exceeded. The adjust high, adjust middle, and adjust low
parameters each set two of the digits on the meter: HHMMLL.
ADJ HOURS HIGH
The adjust hours high parameter is used to set the highest two digits, from
00 to 99.
ADJ HOURS MID
The adjust hours middle parameter is used to adjust the middle two digits,
from 00 to 99.
ADJ HOURS LOW
The adjust hours low parameter is used to adjust the lowest two digits, from
00 to 99. It is not possible to set tenths.
SET TOTL HRS
The set total hours parameter is used to apply the preset high, middle, and
low values to the total (i.e., KSI on-time) hourmeter. First, adjust the preset
values as desired for the total hourmeter. Then, program the Set Total Hours
parameter On, which automatically loads the preset values.
Hourmeter Parameters
Hourmeter “Preset” Settings
- BCT-6200-6CA BCT-6000-6SA BCT-6000-6CA BCT-6250-6SA BCT-6250-6CA BC-620-6SA BC-620-6CA BC-600-6SA BC-600-6CA BC-625-6SA BC-625-6CA BC-620-4SA BC-620-4CA BC-600-4SA BC-600-4CA BC-625-4SA BC-625-4CA SCT-7750-6AC SCT-7750-6CA MV-520-6SA PCT-3510-6SA ST PCT-3510-6CA ST PCT-3510-6SA HB PCT-3510-6CA HB PCT-3500-6SA PCT-3500-6CA PC-300-6SA PC-300-6CA PC-325-4SA PC-325-4CA PC-300-4SA PC-300-4CA PMT-5000-6CA PMT-5000-6SA PMT-4500-6SA PMT-4500-6CA SC-775-6AC SC-775-6SA SC-775-6CA SC-750-4SA SC-750-4CA