9. Diagnostic Codes
The WindSonic outputs a diagnostic (TABLE 9-1) along with each wind
direction and speed measurement. The example datalogger programs in this
manual filter all data when the diagnostic is not 0. Short generated programs
do not filter data based on the WindSonic diagnostic. Both the example
programs in this manual and those generated in SCWin record the number of
times an error flag was set. If the WindSonic is not powered, not connected, is
using the wrong COM port/SDI-12 address, or has missed a sample, the
example programs in this manual will load NaN or -99999 for wind direction
and speed, and the diagnostic (TABLE 9-2). The programs also report the
number of good samples that were used in computing the online statistics. If
the total number of good samples is less than 98% of the expected samples, the
WindSonic may be in need of repair.
TABLE 9-1. Gill WindSonic Diagnostic Codes
Diagnostic Status
Comment
0 Okay All
okay
1
Axis 1 Failed
Insufficient samples,
possible path obstruction
2
Axis 2 Failed
Insufficient samples,
possible path obstruction
4
Both Axis Failed Insufficient samples,
possible path obstruction
8
NVM error
Nonvolatile Memory checksum failed
9
ROM error
Read Only Memory checksum failed
10
Maximum Gain
Questionable wind measurements
TABLE 9-2. Example Datalogger Program Diagnostic Codes
Diagnostic
Datalogger
Type
Comment
NaN
CRBasic
WindSonic not powered, not connected, wrong
COM port/SDI-12 address, or missed sample
─99999
Edlog
WindSonic not powered, not connected, wrong
SDI-12 address, or missed sample
27