33: Z=X*F (P37)
1: 6

X Loc [ A ]

2: nnn

F

Enter TC (%/

°

C) to correct cond. reading.

3: 8Z Loc [ TC_Proces ]

34: Z=X+F (P34)
1: 8

X Loc [ TC_Proces ]

2: 100

F

3: 8

Z Loc [ TC_Proces ]


35: Z=X/Y (P38)
1: 7

X Loc [ Ct100 ]

2: 8

Y Loc [ TC_Proces ]

3: 9

Z Loc [ C25mScm_l ]

EC corrected for temperature.


;Output processing, convention states that the temperature be reported
;with the EC measurement.
;

36: Do (P86)
1: 10

Set Output Flag High (Flag 0)


37: Sample (P70)
1: 1

Reps

2: 3

Loc [ Ct ]


38: Sample (P70)
1: 1

Reps

2: 4

Loc [ Temp_degC ]


39: Sample (P70)
1: 1

Reps

2: 9

Loc [ C25mScm_l ]


*Table 2 Program
02: 0.0

Execution

Interval

(seconds)


*Table 3 Subroutines

End Program