Ashcroft GC55 - Differential Pressure Transducer with Digital Display User Manual

Page 6

background image

6

1. specifications*

Pressure Range*:

75, 100, 150, 250, 300 psid

(as noted on the unit)

Proof Pressure*:

2X F.S.

Differential Pressure Range (DP):

DP=P1(H)-P2(L); as marked on unit

Display Range:

Diff. pressure range of –5 to 105%F.S. or display of

–1999 to 1999

Power supply:

• 4-20ma Output Version: 15-27 Vdc, 80mA
• 1-5 Vdc Output Version: 11-27 Vdc, 60mA

Display:

3

1

2

digit LED (digit height: 10mm)

Display accuracy

DP

: ±(1.0%F.S.+1 digit)

P1, P2 : ±(0.5%F.S.+1 digit)

Update Time:

0.2 s

Media / Wetted Materials:

Fluids and gases compatible with 304SS

(sensor housing) and 17-4ph SS (sensor diaphragm)

output:

Analog output (4-20mA or 1-5Vdc)**:

Accuracy: ± 0.5% FS (Accuracy includes the effects of Linearity,

Hysteresis and Repeatability)

Temperature characteristics

DP

: Zero ±0.1%F.S./°C
: Span ±0.1%F.S./°C

P1, P2 : Zero ±0.05%F.S./°C

: Span ±0.05%F.S./°C

Response Time: 20msec – 10.0 sec (by user)
Output Resolution: 0.2% FS

Pressure switch output:

Type: (2) photo MOS relays, rated to 40Vdc/200mA
Setting Accuacy: ± 1.0% FS
Number of Contacts: 2
Hysteresis/Deadband: Variable (by user)
Window Comparator: 1%F.S. fixed
Delay: 0-2.00s (both ON, OFF)

Load resistance:

10k

Ω

min-500

Ω

max.

operating Temperature:

–10 to 50°C (14 to 122°F)