Pv100, Valve controller – High Country Tek ProValve 100 Series User Manual
Page 23
021-PV100 Rev A
PV100 User Manual
23
Copyright © High Country Tek, Inc.
– 2013
PV100
Valve Controller
Mode 3 and Mode 7: dual coil 2-speed control. DIN1 enables coil A, DIN2 enables output B, DIN3 enables high
speed.
DIN1 is ON, DIN2 is ON, DIN3 is
OFF, coil B is set to the Low/ovr
current setting of 0.3A.
Coil B
(DIN2) has a higher priority
than coil A (DIN1).
DIN1 is ON, DIN2 is ON, DIN3 is
ON, coil B is set to the maximum
current setting of 0.95A.
Coil B
(DIN2) has a higher priority
than coil A (DIN1).
DIN1 is OFF, DIN2 is ON, DIN3 is
OFF, coil B is set to the Low/ovr
current setting of 0.3A.