Modes of operation, Pv100, Valve controller – High Country Tek ProValve 100 Series User Manual
Page 13
021-PV100 Rev A
PV100 User Manual
13
Copyright © High Country Tek, Inc.
– 2013
PV100
Valve Controller
Modes of Operation
The PV100 has 8 modes of operation.
Mode
AIN
DIN1
DIN2
DIN3
0 SD -- OF OR
Speed/Direction
Not Used
Forward Override
Reverse Override
1 DR -- -- HS
Direction
Not Used
Not Used
High Speed
2 SP FW RV --
Speed
Forward Enable
Reverse Enable
Not Used
3 -- FW RV HS
Not Used
Forward Enable
Reverse Enable
High Speed
4 SD EN OF OR
Speed/Direction
Enable
Forward Override
Reverse Override
5 DR EN -- HS
Direction
Enable
Not Used
High Speed
6 SP EN RV --
Speed
Enable
Reverse
Not Used
7 -- EN RV HS
Not Used
Enable
Reverse
High Speed
Mode 0 -
Both speed and direction are controlled by the analog input.
0 to 100% input controls coil A current proportionally.
0 to -100% input controls coil B current proportionally.
DIN2 enables forward override; current output is the override setting for coil A.
DIN3 enable reverse override; current output is the override setting for coil B.
Forward override supersedes reverse override.
Mode 1 -
0 to 100% input enables coil A output.
0 to -100% input enables coil B output.
When the high speed input (DIN3) is off, the speed is set to the minimum output value.
When the high speed input (DIN3) is on, the speed is set to the maximum output value.
Mode 2 -
The speed is controlled proportionally by the analog input of 0 to 100% only.
DIN1 enables coil A in forward direction.
DIN2 enables coil B in reverse direction.
Reverse override supersedes forward override.