PV100

Valve Controller

Modes of Operation

The PV100 has 8 modes of operation.

Mode

AIN

DIN1

DIN2

DIN3

0 SD -- OF OR

Speed/Direction

Not Used

Forward Override

Reverse Override

1 DR -- -- HS

Direction

Not Used

Not Used

High Speed

2 SP FW RV --

Speed

Forward Enable

Reverse Enable

Not Used

3 -- FW RV HS

Not Used

Forward Enable

Reverse Enable

High Speed

4 SD EN OF OR

Speed/Direction

Enable

Forward Override

Reverse Override

5 DR EN -- HS

Direction

Enable

Not Used

High Speed

6 SP EN RV --

Speed

Enable

Reverse

Not Used

7 -- EN RV HS

Not Used

Enable

Reverse

High Speed

Mode 0 -

Both speed and direction are controlled by the analog input.

0 to 100% input controls coil A current proportionally.

0 to -100% input controls coil B current proportionally.

DIN2 enables forward override; current output is the override setting for coil A.

DIN3 enable reverse override; current output is the override setting for coil B.

Forward override supersedes reverse override.

Mode 1 -

0 to 100% input enables coil A output.

0 to -100% input enables coil B output.

When the high speed input (DIN3) is off, the speed is set to the minimum output value.

When the high speed input (DIN3) is on, the speed is set to the maximum output value.

Mode 2 -

The speed is controlled proportionally by the analog input of 0 to 100% only.

DIN1 enables coil A in forward direction.

DIN2 enables coil B in reverse direction.

Reverse override supersedes forward override.