7330 Pro-Stik II

The

BW Controls 7330 Series Magnetostrictive

Level System is an integral assembly that measures

linear motion or liquid level using magnetostrictive

technology. A single level output is provided with field

configurable 4mA and 20mA points in an intrinsically

safe, standard two wire loop-powered configuration.

Magnetostrictive technology is extremely accurate and

requires no calibration during installation. The sensor

works equally well on all clean liquids with a viscosity

of 1500 centipoises or less. Various types of Floats

are available for different applications.

Unlike conventional level instruments, the electronics

are incorporated into the measuring probe and

there is no external electronic housing. This design

utilizes sophisticated Surface Mount Technology

(SMT) integrated into a 5/8” diameter tube, reducing

user’s cost and offers greater options for insertion

and mounting. The self-contained unit provides IP68

protection in a 316 stainless steel enclosure.

The 7330 Pro-Stik II offers unique diagnostic

capabilities. The normal 4 to 20mA output indicates

the position of the float within the span. If the level is

outside of the set span, the output is either 3.9mA or

20.1mA. If the float moves into the Null or Dead Zones

or there is a sensing failure, then the output is 3.8mA

Unpacking

Carefully remove the contents of the shipping carton

and check each item against the packing list before

destroying the packing materials. Any damage must be

reported to the shipping company. If you do not recieve

all of the parts on the packing slip, contact Ametek

at 800-635-0289 (US and Canada) or 248-435-0700

(International).

Most rigid probes are shipped in a Tube. To remove

the metal end cap, use a large, flat blade screw driver

or a metal rod and tap on the inner edge of the cap

until it pivots. Grab the cap and pull it out. Use caution

as the edge of the metal cap may be sharp.

If you have an RMA warranty claim, pack the probe in

a shipping tube or with stiff reinforcement to prevent

the probe from being bent in transit.

Mounting Conditions

1. The 7330 Pro-Stik II Series level system is designed

for industrial applications, but should be mounted

in a location as free as possible from vibration,

corrosive atmospheres, or any possibility of

mechanical damage.

2. Mount the probe in a reasonably accessible location,

away from agitation.

3. Ambient measurement temperature should be

between -40°F and 158°F (-40°C to 70°C).

4. Mount the probe perpendicular with gravity so the

float moves freely along the probe.

CAUTION

When installing probes, do not bend rigid

probes. Permanent damage may result.

Rigid probes, longer than 10 ft., need to

be supported at both ends while handling.

Remove the Caution Tag before installing.

Probes are built with the electronic circuits

sealed inside the tube at the factory. Do not

attempt to open probe or weld on the tube.

5. The Float Retention Clip should be in place at base

of probe after the float is on the tube and the float is

moving smoothly up and down the probe.