0 troubleshooting table – ARI Armaturen ARI-PACO 1,6kN EN User Manual
Page 21
![background image](/manuals/409404/21/background.png)
0040506001 1811
Page 21
Operating and installation instructions
Electric thrust actuator ARI-PACO 1,6 kN
9.0 Troubleshooting table
ATTENTION !
- read point 10.0 and 11.0 prior to dismantling and repair work!
- read point 6.0 before restarting the plant !
Fault
Possible Causes
Remedy
Linear actuator does not
move
power loss
determine cause and correct
fuse burned out
change fuse
linear actuator incorrectly
connected
connect the linear actuator
correctly according to the wiring
diagram
short circuit:
- dampness
determine exact cause,
- dry linear actuator and check
and correct for leaks
- incorrect connection
- correct connection according to
the wiring diagram in the linear
actuator
motor or control is burned out
- determine if the mains voltage
conforms with voltage on the
nameplate. Replace motor or
control.
Plug contacts or cable are not or
not correctly plugged in the
socket bar
Plug contacts or cable firmly in.
Linear actuator switches
between running left and
running right
Motor -operating condenser
defective
Replace motor – operating
condenser
Linear actuator does not go
into the end positions and
vibrates
Load-dependant limit switches
are maladjusted / defective
Remove linear actuator and send
back for repair to the company
Loss of voltage because of too
long connection cables or a too
small cable diameter
Install connection cables
according to the required power
Mains deviations outside the
allowed tolerances
Ensure "clean" electrical supplies
within the tolerances
Too high plant pressure
Reduce plant pressure or employ
appropriate actuating drive
Linear actuator sometimes
fails to work
Lead has a loose contact
Tighten connections on the
clamping strips