9.0 Troubleshooting table

ATTENTION !
- read point 10.0 and 1
1.0 prior to dismantling and repair work!
- read point 6.0 before restarting the plant !

Fault

Possible Causes

Remedy

Linear actuator does not
move

power loss

determine cause and correct

fuse burned out

change fuse

linear actuator incorrectly
connected

connect the linear actuator
correctly according to the wiring
diagram

short circuit:
- dampness

determine exact cause,
- dry linear actuator and check

and correct for leaks

- incorrect connection

- correct connection according to

the wiring diagram in the linear

actuator

motor or control is burned out

- determine if the mains voltage

conforms with voltage on the

nameplate. Replace motor or

control.

Plug contacts or cable are not or
not correctly plugged in the
socket bar

Plug contacts or cable firmly in.

Linear actuator switches
between running left and
running right

Motor -operating condenser
defective

Replace motor – operating
condenser

Linear actuator does not go
into the end positions and
vibrates

Load-dependant limit switches
are maladjusted / defective

Remove linear actuator and send
back for repair to the company

Loss of voltage because of too
long connection cables or a too
small cable diameter

Install connection cables
according to the required power

Mains deviations outside the
allowed tolerances

Ensure "clean" electrical supplies
within the tolerances

Too high plant pressure

Reduce plant pressure or employ
appropriate actuating drive

Linear actuator sometimes
fails to work

Lead has a loose contact

Tighten connections on the
clamping strips