beautypg.com

3 assembly instructions to the mounting on valves, 1 mounting von valve ari-paco 1,6 kn – ARI Armaturen ARI-PACO 1,6kN EN User Manual

Page 11

background image

0040506001 1811

Page 11

Operating and installation instructions

Electric thrust actuator ARI-PACO 1,6 kN

5.3 Assembly instructions to the mounting on valves

If the valve is already mounted at the plant, care must be taken that before the drive
is assembled, no pressure difference occurs in the valve body.
If necessary, close shut-off slide valve or switch off pump

.

5.3.1 Mounting von valve ARI-PACO 1,6 kN

Fig. 4
Mount the linear actuator on a valve in the following way:

- screw the coupling out of the torque protection of the linear actuators.
- bring the valve cone about in the middle of the actuating range.

Bild A:

- push the coupling over the valve stem.

Bild B:

- screw the screw socket with toothed lock washer and splint appropriate to

the valve on the valve stem.

Bild C:

- set linear actuator on the valve.
- fasten linear actuator with two hex screws (M8 x 25) and two spring washers

onto the armature.

Bild D:

- with the hand wheel, move the torque protection so far that the torque

protection lies on the screw socket.

- tighten the coupling by hand and then secure with a wrench ( SW24 ) at an

angle of max. 90°! (see also notice on the housing of the drives)

Bild E:

- push upper and lower setting mark of the travel display to the torque

protection.

- make electrical connections (refer to pt. 6.4 ).

splint

turning

toothed lock washer