4.6 Power supply
At ambient temperatures higher than +70°C or if thermal overloading occurs, the device is
not switched off. Instead, the output power is reduced sufficiently to protect the device.
Earth fault detection (EFD)
If an earth fault is detected in the AS-i system, it is evaluated by means of the EFD LED and
a floating switching output.
In the event of an earth fault, the LED lights up, the floating EFD output is opened and if the
switch is set to "EFD int." the device is switched off. Press the Reset button for at least two
seconds to restart it.
If the switch is set to "EFD ext.", the device continues to operate despite the earth fault.
By pressing the Reset button briefly (< 1 second), you can simulate an earth fault.
Fig. 8
No.
Designation
1
AC input:
Input voltage 85 - 264 V AC,
frequency 45 - 65 Hz
2
DC output:
Output voltage 30 V DC
3
Floating EFD output
4
DC OK LED (green)
5
EFD LED (red)
6
Reset button
7
EFD int./ext. switch
Green "DC OK" LED Lit
Blinking
Off
Meaning
Output voltage > 27 V Output voltage < 27 V
No voltage at output
Description
Output voltage and
current OK
Power supply in operation
but
- Fault at load
- Current consumption >
I
BOOST
- Output short-circuited
Power supply not in
operation because
- No mains voltage
present
- Primary fuse has tripped
- Device is defective