beautypg.com

Specifications – Red Lion CSSG User Manual

Page 2

background image

2

SPECIFICATIONS

1. POWER: Derived from system backplane. 250 mA max. load on power input

of MASTER. Module may be hot-swapped (replaced while powered up).
Modules per Master: A single Master can support up to 11 CSSG1 modules

combined with any 5 other module types. For applications that require
more than 11 CSSG1 modules, please contact technical support.

2. LEDs*:

STS - Status LED shows module condition.
OP1, OP2, OP3 - Indicate status of outputs 1, 2, and 3
ALM - Alarm LED is lit during an internal alarm condition.
* Default configuration.

3. MEMORY: Non-volatile memory retains all programmable parameters. The

MASTER also stores the parameters in order to reprogram any modules that
are replaced.

4. INPUTS:

* After 20 minute warm-up. Accuracy over the 0 to 50°C range includes

the temperature coefficient.

Connection Type:

4-wire bridge (differential)
2-wire (single-ended)

Sample Time: 67 msec (15 readings per second)
Common Mode Range (with respect to input common): 0 to +5 VDC
Common Mode Rejection: > 100 dB, DC to 120 Hz
Temperature Coefficient (ratio metric): 20 ppm/°C max.
Step Response Time: 200 msec max. to within 99% of final process value
Input Impedance: 100 M

Max Continuous Overload: 30 V
PV Range: -30,000 to 30,000
Effective Resolution: 16-bit

5. BRIDGE EXCITATIONS:

Software selectable:

5 VDC, ±2%, 65 mA max.
10 VDC, ±2%, 125 mA max. combined (excitation 1 plus excitation 2).

Temperature coefficient (ratio metric): 20 ppm/°C max.
Max. four 350

 bridges per module.

6. ISOLATION LEVEL: 500 Vrms @ 50/60 Hz for 1 minute between the

following:
OP1 *

OP2 *

OP3

Linear Output
Signal Inputs (the 2 input channels are not isolated from each other)
CS Master Power Supply Input
* Outputs OP1 and OP2 of SSR model are not isolated from each other

7. COMMUNICATIONS: Provided by the CS Master.
8. DISCRETE OUTPUTS:

Outputs 1 and 2 are available as Solid State NFET, or Form A relay. Output

3 is a Form C relay.

Solid State Output:

Type: Switched DC, N Channel open drain MOSFET
Current Rating: 1 A max
VDS ON: 0.3 V @ 1 A
VDS MAX: 30 VDC
Offstate Leakage Current: 0.5 mA max

Form A Relay Output:

Type: N.O.
Current Rating: 3 Amps @ 125 VAC
1/10 HP @ 125 VAC
Life Expectancy: 200,000 cycles at maximum load rating. (Decreasing

load, increasing cycle time, and use of surge suppression such as RC
snubbers increases life expectancy.)

Form C Relay Output:

Type: SPDT
Current Rating: 5 Amps @ 125 VAC or 28 VDC (resistive load)
1/8 HP @ 125 VAC
Life Expectancy: 100,000 cycles at maximum load rating. (Decreasing

load, increasing cycle time, and use of surge suppression such as RC
snubbers increases life expectancy.)

9. CONTROL MODES:

Control: On/Off, P, PI, or PID
Output: Time proportioning or linear

Cycle Time: Programmable from 0.0 to 60.0 sec
Auto-Tune: When selected, sets proportional band, integral time, derivative

time values, and output dampening time

Input Fault Response: Upscale

10. ALARMS:

Modes: Manual

Absolute High Acting

Absolute Low Acting

Deviation High Acting

Deviation Low Acting

Inside Band Acting

Outside Band Acting

Reset Action: Programmable; automatic or latched
Standby Mode: Programmable; enable or disable
Hysteresis: Programmable
Input Fault Response: Upscale

11. ANALOG DC OUTPUT:

Jumper Selectable/programmable for 0-10 VDC, 0-20 mA, or 4-20 mA
Resolution:

Voltage: 500 μV
Current: 1 μA

Accuracy:

0.1% of full scale (18 to 28°C)
0.2% of full scale (0 to 50°C)

Update Time: 0.0 to 60.0 sec
Compliance (for current output only): 500

 max.

Minimum load (voltage output only): 10 K

 min.

Output is independently jumper selectable for either 10 V or 20 mA. The

output range may be field calibrated to yield approximate 10% overrange
and a small underrange (negative) signal.

12. ENVIRONMENTAL CONDITIONS:

Operating Temperature Range: 0 to +50°C
Storage Temperature Range: -40 to +85°C
Operating and Storage Humidity: 85% max relative humidity, non-condensing,

from 0 to +50°C

Vibration According to IEC 68-2-6: 10 to 150 Hz, 0.075 mm amplitude in X,

Y, Z direction 1 g.

Shock According to IEC 68-2-27: Operational 25 g (10 g relay), 11 msec in

3 directions.

Altitude: Up to 2000 meters

13. CERTIFICATIONS AND COMPLIANCES:

SAFETY

UL Listed, File # E302106, UL508, CSA C22.2 No. 14-M05

LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards

IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment for

measurement, control, and laboratory use, Part 1.

ELECTROMAGNETIC COMPATIBILITY

Emissions and Immunity to EN 61326: 2006: Electrical Equipment for
Measurement, Control and Laboratory use.

Immunity to Industrial Locations:

Electrostatic discharge

EN 61000-4-2

Criterion B

4 kV contact discharge

8 kV air discharge

Electromagnetic RF fields EN 61000-4-3

Criterion B

3

10 V/m (80 MHz to 1 GHz)

3 V/m (1.4 GHz to 2 GHz)

1 V/m (2 GHz to 2.7 GHz)

Fast transients (burst)

EN 61000-4-4

Criterion B

power 2 kV

I/O signal 1 kV

I/O signal connected to power 2 kV

Surge

EN 61000-4-5

Criterion B

power 1 kV L to L, 2 kV L to G

signal 1 kV

RF conducted interference EN 61000-4-6

Criterion A

3 Vrms

Emissions:

Emissions

EN 55011

Class A

Notes:

1. Criterion A: Normal operation within specified limits.
2. Criterion B: Temporary loss of performance from which unit self-recovers.
3. The module’s analog input and/or output signals may deviate during

disturbance but self-recover when disturbance is removed.

4. Power supplied from backplane via Master Module.

14. CONSTRUCTION: Case body is burgundy high impact plastic. For indoor

use only. Installation Category II, Pollution Degree 2.

15. CONNECTIONS: Removable wire clamp screw terminal blocks.

Wire Gage: 28-16 AWG terminal gage wire
Torque: 1.96-2.23 inch/lbs (0.22-0.25 N-m)

16. MOUNTING: Snaps on to standard DIN style top hat (T) profile mounting

rails according to EN50022 -35 x 7.5 and -35 x 15.

17. WEIGHT: 7 oz (198.4 g)

±20.000 mVDC

SOFTWARE

SELECTABLE

INPUT RANGE

0.02% of reading +3 μV

ACCURACY *

18 TO 28°C

10 TO 75% RH

0.07% of reading +4 μV

ACCURACY *

0 TO 50°C

0 TO 85% RH

±33.000 mVDC 0.02% of reading +5 μV

0.07% of reading +7 μV

±200.00 mVDC 0.02% of reading +30 μV

0.07% of reading +40 μV