SPECIFICATIONS
1. POWER: Derived from system backplane. 250 mA max. load on power input
of MASTER. Module may be hot-swapped (replaced while powered up).
Modules per Master: A single Master can support up to 11 CSSG1 modules
combined with any 5 other module types. For applications that require
more than 11 CSSG1 modules, please contact technical support.
2. LEDs*:
STS - Status LED shows module condition.
OP1, OP2, OP3 - Indicate status of outputs 1, 2, and 3
ALM - Alarm LED is lit during an internal alarm condition.
* Default configuration.
3. MEMORY: Non-volatile memory retains all programmable parameters. The
MASTER also stores the parameters in order to reprogram any modules that
are replaced.
4. INPUTS:
* After 20 minute warm-up. Accuracy over the 0 to 50°C range includes
the temperature coefficient.
Connection Type:
4-wire bridge (differential)
2-wire (single-ended)
Sample Time: 67 msec (15 readings per second)
Common Mode Range (with respect to input common): 0 to +5 VDC
Common Mode Rejection: > 100 dB, DC to 120 Hz
Temperature Coefficient (ratio metric): 20 ppm/°C max.
Step Response Time: 200 msec max. to within 99% of final process value
Input Impedance: 100 M
Max Continuous Overload: 30 V
PV Range: -30,000 to 30,000
Effective Resolution: 16-bit
5. BRIDGE EXCITATIONS:
Software selectable:
5 VDC, ±2%, 65 mA max.
10 VDC, ±2%, 125 mA max. combined (excitation 1 plus excitation 2).
Temperature coefficient (ratio metric): 20 ppm/°C max.
Max. four 350
bridges per module.
6. ISOLATION LEVEL: 500 Vrms @ 50/60 Hz for 1 minute between the
following:
OP1 *
OP2 *
OP3
Linear Output
Signal Inputs (the 2 input channels are not isolated from each other)
CS Master Power Supply Input
* Outputs OP1 and OP2 of SSR model are not isolated from each other
7. COMMUNICATIONS: Provided by the CS Master.
8. DISCRETE OUTPUTS:
Outputs 1 and 2 are available as Solid State NFET, or Form A relay. Output
3 is a Form C relay.
Solid State Output:
Type: Switched DC, N Channel open drain MOSFET
Current Rating: 1 A max
VDS ON: 0.3 V @ 1 A
VDS MAX: 30 VDC
Offstate Leakage Current: 0.5 mA max
Form A Relay Output:
Type: N.O.
Current Rating: 3 Amps @ 125 VAC
1/10 HP @ 125 VAC
Life Expectancy: 200,000 cycles at maximum load rating. (Decreasing
load, increasing cycle time, and use of surge suppression such as RC
snubbers increases life expectancy.)
Form C Relay Output:
Type: SPDT
Current Rating: 5 Amps @ 125 VAC or 28 VDC (resistive load)
1/8 HP @ 125 VAC
Life Expectancy: 100,000 cycles at maximum load rating. (Decreasing
load, increasing cycle time, and use of surge suppression such as RC
snubbers increases life expectancy.)
9. CONTROL MODES:
Control: On/Off, P, PI, or PID
Output: Time proportioning or linear
Cycle Time: Programmable from 0.0 to 60.0 sec
Auto-Tune: When selected, sets proportional band, integral time, derivative
time values, and output dampening time
Input Fault Response: Upscale
10. ALARMS:
Modes: Manual
Absolute High Acting
Absolute Low Acting
Deviation High Acting
Deviation Low Acting
Inside Band Acting
Outside Band Acting
Reset Action: Programmable; automatic or latched
Standby Mode: Programmable; enable or disable
Hysteresis: Programmable
Input Fault Response: Upscale
11. ANALOG DC OUTPUT:
Jumper Selectable/programmable for 0-10 VDC, 0-20 mA, or 4-20 mA
Resolution:
Voltage: 500 μV
Current: 1 μA
Accuracy:
0.1% of full scale (18 to 28°C)
0.2% of full scale (0 to 50°C)
Update Time: 0.0 to 60.0 sec
Compliance (for current output only): 500
max.
Minimum load (voltage output only): 10 K
min.
Output is independently jumper selectable for either 10 V or 20 mA. The
output range may be field calibrated to yield approximate 10% overrange
and a small underrange (negative) signal.
12. ENVIRONMENTAL CONDITIONS:
Operating Temperature Range: 0 to +50°C
Storage Temperature Range: -40 to +85°C
Operating and Storage Humidity: 85% max relative humidity, non-condensing,
from 0 to +50°C
Vibration According to IEC 68-2-6: 10 to 150 Hz, 0.075 mm amplitude in X,
Y, Z direction 1 g.
Shock According to IEC 68-2-27: Operational 25 g (10 g relay), 11 msec in
3 directions.
Altitude: Up to 2000 meters
13. CERTIFICATIONS AND COMPLIANCES:
SAFETY
UL Listed, File # E302106, UL508, CSA C22.2 No. 14-M05
LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards
IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment for
measurement, control, and laboratory use, Part 1.
ELECTROMAGNETIC COMPATIBILITY
Emissions and Immunity to EN 61326: 2006: Electrical Equipment for
Measurement, Control and Laboratory use.
Immunity to Industrial Locations:
Electrostatic discharge
EN 61000-4-2
Criterion B
4 kV contact discharge
8 kV air discharge
Electromagnetic RF fields EN 61000-4-3
Criterion B
3
10 V/m (80 MHz to 1 GHz)
3 V/m (1.4 GHz to 2 GHz)
1 V/m (2 GHz to 2.7 GHz)
Fast transients (burst)
EN 61000-4-4
Criterion B
power 2 kV
I/O signal 1 kV
I/O signal connected to power 2 kV
Surge
EN 61000-4-5
Criterion B
power 1 kV L to L, 2 kV L to G
signal 1 kV
RF conducted interference EN 61000-4-6
Criterion A
3 Vrms
Emissions:
Emissions
EN 55011
Class A
Notes:
1. Criterion A: Normal operation within specified limits.
2. Criterion B: Temporary loss of performance from which unit self-recovers.
3. The module’s analog input and/or output signals may deviate during
disturbance but self-recover when disturbance is removed.
4. Power supplied from backplane via Master Module.
14. CONSTRUCTION: Case body is burgundy high impact plastic. For indoor
use only. Installation Category II, Pollution Degree 2.
15. CONNECTIONS: Removable wire clamp screw terminal blocks.
Wire Gage: 28-16 AWG terminal gage wire
Torque: 1.96-2.23 inch/lbs (0.22-0.25 N-m)
16. MOUNTING: Snaps on to standard DIN style top hat (T) profile mounting
rails according to EN50022 -35 x 7.5 and -35 x 15.
17. WEIGHT: 7 oz (198.4 g)
±20.000 mVDC
SOFTWARE
SELECTABLE
INPUT RANGE
0.02% of reading +3 μV
ACCURACY *
18 TO 28°C
10 TO 75% RH
0.07% of reading +4 μV
ACCURACY *
0 TO 50°C
0 TO 85% RH
±33.000 mVDC 0.02% of reading +5 μV
0.07% of reading +7 μV
±200.00 mVDC 0.02% of reading +30 μV
0.07% of reading +40 μV