ORDERING INFORMATION

Maximum Count Rate:

All Count Sources except Input B: 10 Hz
Input B Count Source:

With Timer Input Filter ON: 10 Hz
With Timer Input Filter OFF: 500 Hz

5. TIMER SIGNAL INPUTS (INP A and INP B)

DIP switch selectable pull-up (7.8 K

) or pull-down (3.9 K) resistors

determine active high or active low input logic.

Input A Trigger levels: V

IL

= 1.25 V max; V

IH

= 2.75 V min; V

MAX

= 28 VDC

Input B: Trigger levels: V

IL

= 1.0 V max; V

IH

= 2.4 V min; V

MAX

= 28 VDC

Inputs A and B:

Timer Input Pulse Width: 1 msec min.
Timer Start/Stop Response Time: 1 msec max.
Filter: Software filtering provided for relay or switch contact debounce.

Filter enabled or disabled through programming. If enabled, results in
50 msec start/stop response time for successive pulses applied to the
same input terminal.

6. RESET/USER INPUT Programmable Function Input:

DIP switch selectable pull-up (7.8 K

) or pull-down (3.9 K) resistor

that determines active high or active low input logic.

Trigger levels: V

IL

= 1.0 V max; V

IH

= 2.4 V min; V

MAX

= 28 VDC

Response Time: 10 msec typ.; 50 msec debounce (activation and release)

7. COMMUNICATIONS:

RS485 SERIAL COMMUNICATIONS

Type: RS485 multi-point balanced interface (isolated)
Baud Rate: 300 to 38400
Data Format: 7/8 bits; odd, even, or no parity
Bus Address: 0 to 99; max 32 meters per line

RS232 SERIAL COMMUNICATIONS

Type: RS232 half duplex (isolated)
Baud Rate: 300 to 38400
Data Format: 7/8 bits; odd, even, or no parity

8. MEMORY: Nonvolatile E

2

PROM retains all programming parameters and

timer/count values when power is removed.

9. OUTPUT:

Relay: Form C contacts rated at 5 amps @ 120/240 VAC or 28 VDC (resistive

load), 1/8 H.P. @ 120 VAC (inductive load)

10. CONNECTIONS:

Internal removable terminal blocks are used for power and signal wiring.
Remove end plates with ¼" nut driver. For LD4 versions, all wiring is on right
side of unit. For LD2 versions, power and signal wiring connections are on
the right side and the relay and serial output options are on left side.
Wire Strip Length: 0.4" (10 mm)
Wire Gage: 24-12 AWG copper wire, 90°C rated insulation only
Torque: 5.3 inch-lbs (0.6 N-m) max
Cable Diameter: Outside diameter must be 0.181" (4.6 mm) to 0.312" (7.9

mm) to maintain NEMA 4 rating of cord grips.

11. ENVIRONMENTAL CONDITIONS:

Operating temperature: 0 to 65 °C
Storage temperature: -40 to 70 °C
Operating and storage humidity: 0 to 85% max. RH (non-condensing)
Vibration According to IEC 68-2-6: Operational 5 to 150 Hz, in X, Y, Z

direction for 1.5 hours, 2 g’s (1g relay).

Shock According to IEC 68-2-27: Operational 30 g’s (10g relay), 11 msec in

3 directions.

Altitude: Up to 2,000 meters

12. CERTIFICATIONS AND COMPLIANCES:

SAFETY
UL Listed, File # E137808, UL508, CSA C22.2 No. 14-M95

LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards
Type 4X Enclosure rating, UL50

IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment for

measurement, control, and laboratory use, Part 1.

IP65 Enclosure rating, IEC 529
ELECTROMAGNETIC COMPATIBILITY
Emissions and Immunity to EN 61326: Electrical Equipment for Measurement,

Control and Laboratory use.

Notes:

1. Criterion A: Normal operation within specified limits.

13. CONSTRUCTION: Aluminum enclosure, and steel side panels with textured

black polyurethane paint for scratch and corrosion resistance protection. Meets
NEMA 4X/IP65 specifications. Installation Category II, Pollution Degree 2.

14. WEIGHT:

LD2T06P0 - 4.5 lbs (2.04 kg)
LD4T06P0 - 10.5 lbs (4.76 kg)

Class B

EN 55011

Emissions

Emissions:

0.5 cycle

Criterion A

3 V/rms

EN61000-4-11

Voltage dip/interruptions

Criterion A

EN 61000-4-6

RF conducted interference

1 kV L-L,

Criterion A

EN 61000-4-5

Surge

1 kV signal

2 kV power

Criterion A

EN 61000-4-4

Fast transients (burst)

2 kV L&N-E power

10 V/m

Criterion A

EN 61000-4-3

Electromagnetic RF fields

8 kV air discharge

4 kV contact discharge

Criterion A

EN 61000-4-2

Electrostatic discharge

Immunity to Industrial Locations:

1.0 I

NSTALLING

THE

M

ETER

INSTALLATION

The meter meets NEMA 4X/IP65 requirements when properly installed.

INSTALLATION ENVIRONMENT

The unit should be installed in a location that does not exceed the operating

temperature. Placing the unit near devices that generate excessive heat should be
avoided. The unit should only be cleaned with a soft cloth and neutral soap
product. Do NOT use solvents.

Continuous exposure to direct sunlight may accelerate the aging process of

the front overlay. Do not use tools of any kind (screwdrivers, pens, pencils, etc.)
to operate the keypad of the unit.

MOUNTING INSTRUCTIONS

This display is designed to be

wall mounted or suspended
from a ceiling truss or other
suitable structure capable
of supporting the LDT.
Caution should be exercised
when hanging the display to
provide for the safety of
personnel. If hanging the LDT,
run the suspension cables (or
chains) through the mounting
bracket holes. For wall mounting
use #10-32 size bolts.

MOUNTING HOLE (.281")

MUST BE
CONNECTED TO

TERMINAL #3 (TBA)

MODEL NO.

DESCRIPTION

PART NUMBER

LD

2.25" High 6-Digit Red LED Timer/Cycle Counter w/ Relay Output &
RS232/RS485 Serial Communications

LD2T06P0

4" High 6-Digit Red LED Timer/Cycle Counter w/ Relay Output &
RS232/RS485 Serial Communications

LD4T06P0

LD Plug

Panel Meter Plug for LD models

LDPLUG00