beautypg.com

4 module 4 - s, Etpoint, Utput – Red Lion LDT User Manual

Page 10: Arameters

background image

10



will restore the output to the same state it was at before the meter was

powered down.



will activate the output at power up.



will deactivate the

output at power up. This parameter is not active when the Setpoint Action is
selected for timed output mode.

SETPOINT OUTPUT POWER-UP STATE

Stops the Timer when the Setpoint output activates (



) or deactivates

(



). Select



if the output should not affect the Timer Run/Stop status.

The Timer Stop condition is cleared when a Timer Reset occurs, or a Time

Start edge is applied on the Timer input.

STOP TIMER

SETPOINT OUTPUT TIME-OUT

SPT ACTION DESCRIPTION

OUTPUT ACTIVATES

OUTPUT DEACTIVATES



Latched Output Mode

When Time or Count

= Setpoint On value

At Manual Reset

(if



=



)



Timed Output Mode

When Time or Count

= Setpoint On value

After Setpoint

Output Time-Out



On-Off Output Mode

When Time or Count



Setpoint On value

When Time or Count



Setpoint Off value

This parameter is only active if the Setpoint Action is set to Timed Output mode

(



). Enter the time duration the Setpoint Output will remain ON once it is

activated. This value is always entered in minutes, seconds, and hundredths of
seconds format. The maximum value is 99 minutes 59.99 seconds.



to



SETPOINT ON

This parameter determines when the Setpoint output will activate. The output

can activate at a programmed Setpoint Value or can be set to activate when the
Timer starts (



) or stops (



).

Selecting



displays a sub-menu where the Setpoint Value is entered. If

the Setpoint is assigned to the Timer, the value is entered in the same display
format as the selected Timer Range.

Automatically resets the Setpoint Assigned display value when the Setpoint

Output activates (



) or deactivates (



). Select



if the output should

not cause a display reset.

TIMER/COUNTER AUTO RESET

Select



to have the Setpoint Output deactivate (reset) when the Setpoint

Assigned display resets. Reset can occur by the RST key or the User Input,
if programmed for that function. Select



if the Setpoint output should not

reset when the display resets.

SETPOINT OUTPUT RESET WITH DISPLAY RESET









SETPOINT OFF

The Setpoint Off parameter only appears if the Setpoint Action is set to

On-Off Output mode (



). In this mode, the Setpoint OFF parameter

determines when the Setpoint Output will deactivate. The output can be
programmed to deactivate at a Setpoint Off Value or can be set to deactivate
when the Timer starts (



) or stops (



).

Selecting



displays a sub-menu where the Setpoint Off Value is

entered. If the Setpoint is assigned to the Timer, the value is entered in the same
display format as the selected Timer Range.







































5.4 MODULE 4 - S

ETPOINT

O

UTPUT

P

ARAMETERS

(



)

PAR

Setpoint

Output Action

Setpoint

Assignment

Setpoint On

Timer/Counter

Auto Reset

Setpoint Off

Stop Timer

Setpoint

Output

Time-out

Setpoint

Output Reset

with Display

Reset

SP-ASN

4-SPt

SP-ACt

SP-ON

SP-OFF

O-tOUt

StOP-t

AUtO-r

OrSt-r

Pro

Setpoint

Output

Power-up

State

O P-UP

PARAMETER MENU

Module 4 is the programming module for the Setpoint Output parameters.

Some parameters will not appear depending on the Setpoint Assignment and
Setpoint Output Action selected.

Select the display for Setpoint assignment.

SETPOINT ASSIGNMENT









SETPOINT OUTPUT ACTION

This parameter selects the action of the Setpoint output as shown below.























to











to











