4.3.e Operating Pressures and Water Flow Rates
CAUTION
- Failure to heed the following may result in equipment damage.
Water flow exceeding maximum flow rate may damage titanium condenser; such
damage will not be covered under the equipment warranty.
Operating Pressure
A bypass valve is required when water flow may exceed maximum flow rates. The maximum static (or
operating pressure) is 50 pounds-per-square-inch (PSI).
Water Flow Rates
Design the plumbing system to maintain ideal flow through the heat pump under worst-case conditions
(i.e.: filter fouled to 10 PSI rise). These specifications relate to the heat pump only. Code-specified whole
system turnover rates must be satisfied. Contact AquaCal AutoPilot Technical Support for guidance
regarding testing for water flow rate.
SOURCE-SIDE
MODEL
CONDENSER
TYPE
FLOW RATES
MINIMUM
MAXIMUM
IDEAL
WS03
Titanium
N/A
N/A
N/A
Cupro-Nickel
10 GPM
14 GPM
12 GPM
WS05
Titanium
N/A
N/A
N/A
Cupro-Nickel
20 GPM
25 GPM
22 GPM
WS10
Titanium
30 GPM
70 GPM
45 - 50 GPM
Cupro-Nickel
50 GPM
60 GPM
55 GPM
SP05
Titanium
25 GPM
70 GPM
45 - 50 GPM
Cupro-Nickel
N/A
N/A
N/A
Table 9
POOL-SIDE
MODEL
CONDENSER
TYPE
FLOW RATES
MINIMUM
MAXIMUM
IDEAL
WS03
Titanium
25 GPM
70 GPM
45 - 50 GPM
Cupro-Nickel
N/A
N/A
N/A
WS05
Titanium
25 GPM
70 GPM
45
– 50 GPM
Cupro-Nickel
N/A
N/A
N/A
WS10
Titanium
N/A
N/A
N/A
Cupro-Nickel
50 GPM
60 GPM
55 GPM
SP05
Titanium
25 GPM
70 GPM
45
– 50 GPM
Cupro-Nickel
20 GPM
25 GPM
25 GPM
Table 10
A
1,000 BTU’s require a minimum of .45 GPM of water flow.
Example (130,000 BTU = 58.5 GPM)