4.3.e Operating Pressures and Water Flow Rates

CAUTION

- Failure to heed the following may result in equipment damage.

Water flow exceeding maximum flow rate may damage titanium condenser; such
damage will not be covered under the equipment warranty.

Operating Pressure

A bypass valve is required when water flow may exceed maximum flow rates. The maximum static (or
operating pressure) is 50 pounds-per-square-inch (PSI).

Water Flow Rates

Design the plumbing system to maintain ideal flow through the heat pump under worst-case conditions
(i.e.: filter fouled to 10 PSI rise). These specifications relate to the heat pump only. Code-specified whole
system turnover rates must be satisfied. Contact AquaCal AutoPilot Technical Support for guidance
regarding testing for water flow rate.

SOURCE-SIDE

MODEL

CONDENSER

TYPE

FLOW RATES

MINIMUM

MAXIMUM

IDEAL

WS03

Titanium

N/A

N/A

N/A

Cupro-Nickel

10 GPM

14 GPM

12 GPM

WS05

Titanium

N/A

N/A

N/A

Cupro-Nickel

20 GPM

25 GPM

22 GPM

WS10

Titanium

30 GPM

70 GPM

45 - 50 GPM

Cupro-Nickel

50 GPM

60 GPM

55 GPM

SP05

Titanium

25 GPM

70 GPM

45 - 50 GPM

Cupro-Nickel

N/A

N/A

N/A

Table 9

POOL-SIDE

MODEL

CONDENSER

TYPE

FLOW RATES

MINIMUM

MAXIMUM

IDEAL

WS03

Titanium

25 GPM

70 GPM

45 - 50 GPM

Cupro-Nickel

N/A

N/A

N/A

WS05

Titanium

25 GPM

70 GPM

45

– 50 GPM

Cupro-Nickel

N/A

N/A

N/A

WS10

Titanium

N/A

N/A

N/A

Cupro-Nickel

50 GPM

60 GPM

55 GPM

SP05

Titanium

25 GPM

70 GPM

45

– 50 GPM

Cupro-Nickel

20 GPM

25 GPM

25 GPM

Table 10

A

1,000 BTU’s require a minimum of .45 GPM of water flow.

Example (130,000 BTU = 58.5 GPM)