beautypg.com

Controlling irrigation and rainwater runoff, Planning for condensation, Mounting pad requirements – Aquacal LTM0266 User Manual

Page 19: Anchoring heat pump to pad, Plumbing

background image

Page 13

4.2.b Controlling Irrigation and Rainwater Runoff

Avoid placing heat pump in direct rainwater runoff from roofs. If the roof slope directs runoff into the heat
pump, a gutter or rain shield is required on the roof edge above the heat pump. Avoid water spraying onto
the heat pump by re-locating or adjusting irrigation.

4.2.c Planning for Condensation

Insulated evaporator and refrigeration components prevent significant volumes of condensation from
forming inside the unit when operating.

4.2.d Mounting Pad Requirements

Equipment pad is to be constructed of concrete, or other code-approved materials sufficient to

support the weight of the heat pump.

Pad is to be elevated to provide adequate drainage to base of heat pump.

Pad is to be essentially level and extend in all directions (at least) 6" beyond the base of the heat

pump. Under no circumstances should the heat pump be installed directly onto the earth.

For purposes of sound abatement, equipment base is not to be joined to a building

’s foundation or

placed directly on concrete floors inside building. For inside installations, vibration dampeners are
recommended between equipment and concrete floor to avoid harmonic drone vibration during
equipment operation.

Do not place one water source heat pump directly on top of another. A structural metal rack is

required wh

en pumps are “stacked”. See local code requirements for rack specifications. Water

source heat pumps may be racked a maximum of two high.

Equipment pad and racks must meet all requirements of authorities having code-related jurisdiction.

4.2.e Anchoring Heat Pump to Pad

Follow all relevant local, state, or national requirements regarding wind load anchoring. Contact AquaCal
AutoPilot to obtain the correct anchoring kit information. Please have the heat pump model number ready
when contacting AquaCal AutoPilot.

4.3 Plumbing

Plumbing diagrams are provided in this section as a planning guide for installing equipment.

The heat pump must receive water flow within the specified minimum and maximum ranges. If the
installation does not closely follow any of the supplied plumbing diagrams, AquaCal AutoPilot Technical
Support is available for installation advice and guidance.

Install a bypass valve whenever water flow rate may exceed maximum rating. See Operating Pressures
on page 19 for specific maximum rates. Contact AquaCal AutoPilot Technical Support for guidance
regarding testing for water flow rate.

CAUTION

- Failure to heed the following may result in equipment damage.

Water flow exceeding maximum flow rates may damage heat pump and will not be
covered under equipment warranty.