Troubleshooting, If the storage blade does not power up, Diagnostic questions – HP D2220sb-Storage-Blade User Manual

Page 32: Is the storage blade operating properly

background image

Troubleshooting 32

Troubleshooting

If the storage blade does not power up

If the D2220sb does not start:

1.

Be sure that the D2220sb is installed adjacent to the partner server blade.

2.

Use the Onboard Administrator to be sure that sufficient power is available.

3.

Use the Onboard Administrator to verify that sufficient cooling is available.

4.

Restart the partner server blade.

IMPORTANT:

If the system does not restart, proceed to "Diagnostic Questions (on page

32

)."

5.

Verify that the D2220sb front panel health LED changes from flashing amber to solid green.

Diagnostic questions

Is the storage blade operating properly?

Answer

Possible reasons

Possible solutions

No

The D2220sb is not installed adjacent to the

partner server blade.

Verify that the D2220sb is installed adjacent to the

partner server blade. See "Installation guidelines

(on page

12

)."

The partner server blade was not restarted
after the D2220sb was installed.

Restart the server blade.

The D2220sb is not properly seated in the

device bay.

1

Power down the partner server blade.

2

Reseat the D2220sb in the device bay.

3

Restart the server blade.

Insufficient power is available to operate the

D2220sb.

Remove any unused server blades, D2220sbs,

or interconnect devices.

Verify that the enclosure has sufficient power

supply capacity available to operate all
installed devices.

Verify that the enclosure power settings will

enable the D2220sb to start.

Add power supplies to meet the power
requirement.

Insufficient or improperly located enclosure

cooling fans

Verify that a sufficient number of cooling fans

are in the enclosure.

Verify that the cooling fans are properly

configured for the devices installed in the
enclosure.

The drive drawer was open too long and

triggered overtemperature alerts.

Close the drive drawer and wait for normal

operating temperatures to resume. A green health