Pipe Length Elevation and Additional Quantity of Gas

• The outdoor unit is charged with the

refrigerant for standard pipe length.

• When the connecting pipe length is longer

than standard length, additional refrigerant

should be added into the unit according

the above table through the service port on

3-way service valve on the outdoor unit.

• Please maintain the shortest distance (3 to 5

meters) and shortest misalignment possible

between the indoor and outdoor units.

• The maximum allowance length and height

is based on reliability.

• Exceeding the maximum may cause poor

performance or malfunction.

• When the outdoor unit is installed above

the indoor unit, oil trap should be installed

every 5-7 meters.

Outdoor unit

Outdoor unit

Maximum length

Maximum length

indoor unit

Maximum height

indoor unit

Oil trap

Rooftop installation

1 If the outdoor unit is installed on a roof

structure, be sure to level the unit.

2 Ensure the roof structure and anchoring

method are adequate for the unit location.

3 If the outdoor unit is installed on roof

structures or external walls, this may result in

excessive noise and vibration, and may also

be classed as non-serviceable installation.

Piping length under 5m

Piping length 5m or more

Product

suction Pipe

diameter

Discharge Pipe

diameter

standard

length (m)

Maximum

length (m)

Maximum

height (m)

Additional

refrigerant

(g/m)

EXM18HV1WE 6.35mm (1/4”)

9.52mm (3/8”)

5

20

10

15

EXM24HV1WE

6.35mm (1/4”)

9.52mm (3/8”)

5

20

10

15

caution

Maximum height

This manual is related to the following products: