Pump Done

Operation test

Check After installation

• Connect the hose of manifold valve to the

charge port of stop valve on the gas pipe side of

the outdoor unit.

• Close the stop valve on the gas pipe side

almost completely.

• Fully close the stop valve on the liquid pipe side.
• Turn on the unit in COOL mode.
• Fully close the stop valve on the gas pipe side

when the pressure gauge shows 1 - 0.5 kgf/cm

2

(100 ~ 50 kPa).

• Stop the test run operation by turn the unit off

and all the refrigerant gas have been collected

in the outdoor unit.

1

Before Operation test

• Do not switch on power before installation is

finished completely.

• Electric wiring must be connected correctly

and securely.

• Stop valves of the connection pipes should

be fully opened.

• All the impurities such as scraps and waste

must be cleared from the unit.

2

Operation test Method

• Switch on power and press “ON/OFF” button

on the remote controller to start the operation.

• Press MODE button to select the COOL,

HEAT (if applicable), FAN to check if all the

functions work well.

• When the ambient temperature is lower than

16°C), the unit can not be set on the remote

control to work in COOL mode. Please use

the Emergency Operation mode which is

used only when the remote is unavailable or

in case of maintenance.

Manual control

button

Manual control button

When relocating or disposing of the air

conditioner, pump down the system following

the procedure below so that no refrigerant is

released into the atmosphere.

items to be checked

Possible malfunction

Has the unit been fixed

firmly?

The unit may drop, shake or

emit noise.

Have you done the

refrigerant leakage test?

It may cause insufficient

cooling (heating)

Is thermal insulation

sufficient?

It may cause condensation.

Is water drainage

satisfactory?

It may cause water leakage.

Is the voltage in

accordance with the

rated voltage marked on

the nameplate?

It may cause electric

malfunction or damage the

unit.

Is the electric wiring

or piping connection

installed correctly and

securely?

It may cause electric

malfunction or damage the

parts.

Has the unit been

securely earthed?

It may cause electrical

leakage.

Is the power cord

specified?

It may cause electric

malfunction or damage the

parts.

Is the inlet or outlet

blocked?

It may cause insufficient

cooling (heating)

Is the length of

connection pipes and

refrigerant capacity

recorded?

The refrigerant capacity is

not accurate.