Refrigerant pipe connection

step 5: installation of Connection Pipe

Copper tube

Flare nut

1 Flaring work
Main cause for refrigerant leakage is due to

defects in the flaring work. Carry out correct flaring

work using the following procedure:

A: Cut the pipes and the cable.
• Use the piping kit accessory (if applicable) or

pipes purchased locally.

• Measure the distance between the indoor and

the outdoor unit.

• Cut the pipes a little longer than the measured

distance.

• Cut the cable 1.5m longer than the pipe length.

It is not possible to put them on after flaring work.
D: Flaring work.
• Carry out flaring work using flaring tool as

shown below.

Handle

bar

bar

Yoke

Cone

Pipe

Copper pipe

Clamp handle

Red arrow mark

• Firmly hold copper pipe in a die according to

the dimension shown in the table below.

Oblique Roughness

burr

B: Burr removal
• Completely remove all burrs from the cut

cross section of pipe/tube.

• Face the end of the copper pipe/tube in a

downward direction as you remove burrs in

order to avoid burrs dropping into the tubing.

E: Check
• Compare the flare work with the adjacent

diagram.

• If the pipe has any defect, cut off the enlarged

section and redo the work.

Pipe

Smooth all around

Face down

Reamer

Improper flaring

Inclined

Cracked

Damaged

surface

Uneven

thickness

Even length all

around

C: Putting flare nut on
• Remove flare nuts attached to indoor and

outdoor unit, then put them on pipe/tube

having completed burr removal.

• Make an independent covering for each

pipe with the appropriate tubular isolation.

caution

Outer diam. (mm)

A (mm)

Max.

Min.

Ф6.35 (1/4”)

1.3

0.7

Ф9.52 (3/8”)

1.6

1.0

Ф12.70 (1/2”)

1.8

1.0

Ф15.88 (5/8”)

2.4

2.2