Test and running, 22 when using the vacuum pump gas leakage check, Electrical safety check – Electrolux EXM24HV1WE User Manual

Page 22

background image

22

When Using the Vacuum Pump

Gas Leakage Check

test and Running

Electrical safety Check

1 Completely tighten the flare nuts on A, B, C

and D, connect the manifold valve charge

hose (blue) to the charge port of the low

pressure valve (3-way valve) on the gas pipe

side.

2 Connect the other charge hose (yellow) of

manifold to the vacuum pump.

3 Fully open the handle Lo of the manifold

valve.

4 Open the vacuum pump for vacuumization.

At the beginning, slightly loose the flare nut

of the low pressure valve to check if there

is air coming inside (If operation noise of

the vacuum pump has been changed, the

reading of multimeter is 0 instead of minus).

Then tighten the flare nut.

5 Keep vacuuming for more than 15 minutes

and make sure the reading of multimeter is

-1.0 x 10

5

Pa (-76cmHg). Then fully close

the handle Lo of manifold valve and stop the

operation of the vacuum pump.

6 Turn the stem of the stop valve b (2-way

valve) about 45° counterclockwise for 6~7

seconds after the gas coming out, then

tighten the flare nut again. Make sure the

pressure display in the pressure indicator is a

little higher than the atmosphere pressure.

7 Remove the charge hose from the low

pressure charge port.

8 Fully open the valve stems of A (3-way valve)

and b (2-way valve).

9 Securely tighten the stem cap.

1 Soap water method:

Apply soap water or liquid neutral detergent on

all valves and pipe connections (A, b, C and D,

refer to the figure below) involved in installation

by a soft brush to check for leakage.
If bubbles come out, the pipes have leakage.

2 Leak detector

Use the leak detector to check for leakage.

Perform the electric safe check after completing the

installation:

1 Earthing work

After finishing earthing work, measure the

earthing resistance by visual detection and

earthing resistance tester.

2 Electrical leakage check

(performing during test running)
During test operation after finishing installation,

the service person can use the electric probe

and multimeter to perform the electrical leakage

check. Turn off the unit immediately if refrigerant

leakage happens. Check and find out the

solution ways till the unit operate properly.

Outdoor Unit

Manifold

valve

Multimeter

-76cmHg

Lo Handle

Hi Handle

Charging hose

Low pressure

valve

Charging

hose

Vacuum Pump

Indoor unit

check points

Liquid pipe

Gas pipe

Outdoor

Unit

Outdoor unit

check points

2-way

valve
3-way

valve

b

D

C

A